Commissioning
77/ 122
Powerlift prefabricated pumping station
Menu
point
Unit
Pump type
Settings with level sensor:
A
+
B
C
D
E
AL
PL
BL
OFF
AL
PL
BL
OFF
AL
*
PL
*
BL
*
OFF
*
After-running
period
s
0
**
0
0
0
Maximum
current
– 1
***
Maximum
current
– 2
***
A
SAT-Q 300/65/D
5.1
SAT-Q 300/80/D
5.1
SAT-Q 400/65/D
6.7
SAT-Q 400/80/D
6.7
SAT-Q 550/80/4/D
9.0
SAT-Q 750/80/D
15.9
SAT-Q 1000/100/D
21.6
SAT-Q 1000/100/4/D
20.0
SAT-Q 1500/100/D
28.8
SAT-Q 300/80/4/D
5.8
KL-AT-M 200/4/80/D-Ex
4.1
KL-AT-M 300/4/80/D-Ex
5.8
KL-AT-M 400/4/80/D-Ex
7.3
KL-AT-V 400/2/80/D-Ex
6.7
KL-AT-V 400/4/100/D-
Ex
7.3
KL-AT-V 550/2/80/D-Ex
8.7
Level
control
–
Internal converter
Float
switch
4-20mA
interface
20 mA =>
level
cm
–
–
–
400
Language
–
German
*
Previously set under “level control” menu item = Set
4-20mA Interface
“and under”
20 mA => Level =
400
.
**
Value = 0 with version with air bubble injection. With version without air bubble injection, value assessment
during trial run: Water level must remain approx. 5 cm under lower edge of back pressure hole.
***
With Level Control PS 2 Control System: Setting via separate motor protection switch.