Commissioning
83/ 122
Powerlift prefabricated pumping station
The water level at the "after-running period OFF” is located at approx. 50 mm below the lower
edge of the back pressure bell.
The tank can be filled via the inlet pipe or via the inspection opening.
Starting automatic mode:
Î
Press both buttons to start automatic
operation of Pumps 1 and 2.
Anzeige
Störung
Pumpe 1 Pumpe 2
Betrieb
Nachlauf
Automatik
Handbetrieb
Hochwasser-
Alarm
MultiControl Duo
Auswahl
Quittung
HAND
0
AUTO
Pumpe 1 Pumpe 2
Î
Fill the tank
When the water level reaches the “Base load”
(BL) level, Pump 1 switches on.
Î
Interrupt the inlet.
BL
When the water reaches the “OFF” level, Pump
1 switches off.
IMPORTANT
With a combination of open back
pressure bell without air bubble injection: Switch
on Pump 1 manually, measure the time until the
water level is approx. 50 mm below the back
pressure bell and set this time in the control as
the after-running period for both pumps.
OFF
Î
Fill the tank
When the water level reaches the “Base load”
(BL) level, Pump 2 switches on.
Î
Interrupt the inlet.
BL
When the water reaches the “OFF” level, Pump
2 switches off.
IMPORTANT
With a combination of open back
pressure without air bubble injection:The water
level will be lowered by the after-running period
to the “after-running level OFF” (ARP OFF) level.
Then Pump 2 switches off.
OFF
and/or
ARP OFF