Technical Data
119/ 122
Powerlift prefabricated pumping station
6.5 Level Control PS 2 Control System
6.5.1 Key data
Key data
Values
Operating voltage:
~ 400 V (L1, L2, L3, N, PE), 50 Hz
Control voltage:
230 VAC, 50 Hz
Motor current limitation
0.3 A to 12 A (with duo: adjustable for each pump)
Power intake (contactors operated):
< 20 VA
Connected load, maximum:
P2
>
5.5 kW
Protection type, controller:
IP 54
Isolated alarm contact:
3 A
Fuse (alarm output):
5 x 20 AT
Rechargeable accumulator (mains-
independent alarm):
9 V, 200 mAh (approx. 5 to 6 h)
Alarm volume:
85 dB
Dimension:
Object related (W x H x D)
*
incl. cable glands
6.5.2 Circuit diagram
Object documentation.