Technical Data
103/ 122
Powerlift prefabricated pumping station
Performance diagram SAT-Q 750/80/D
Eff. 43,6%
▕◄
Application range
►▏
Head
H
/ m
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Q
/ m³/h
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
- DRP 750/2/80 A0HT5
SAT-Q 750/80/D
Anwendungsbereich
6.2.5 SAT-Q 300/80/4/D and SAT-Q 550/80/4/D
Characteristic data and use limits
Key data
SAT-Q
300/80/4/D
550/80/4/D
Type of cable for connection cable:
4G1.5+3x1
4G2.5+3x1
Pump motor operating voltage [V]:
400
400
Frequency [Hz]:
50
50
Pump motor speed [1/min.]:
1,428
1,397
Pump motor power input P1 [kW]:
2.9
5.2
Pump motor output P2 [kW]:
2.2
4.0
Pump motor nominal current [A]:
5.8
9.0
Maximum starts per hour:
30
30
Maximum ball through-flow and/or through-flow [mm]:
80
70 x 60
Medium temperature range [°C]:
40
40
Fluid pH-value:
6 – 14
6 – 14
Fluid viscosity [mm²/s]:
1.005
1.005
Medium density [kg/ m³]:
1,100
1,100
Weight [kg]:
87
82