DCS500 Pin and Parameter list
A 23
Group 6: DATA LOGGER
DLOG.[IN1]
Input of DATA_LOGGER-function block.
( S14/16 )
Selects the signal which is measured in channel 1.
601
FB_I: C4
SC: -
HL: 19999
LL: 0
D: 12102
U: -
DLOG.[IN2]
Input of DATA_LOGGER-function block.
( S14/16 )
Selects the signal which is measured in channel 2.
602
FB_I: C4
SC: -
HL: 19999
LL: 0
D: 10501
U: -
DLOG.[IN3]
Input of DATA_LOGGER-function block.
( S14/16 )
Selects the signal which is measured in channel 3.
603
FB_I: C4
SC: -
HL: 19999
LL: 0
D: 10505
U: -
DLOG.[IN4]
Input of DATA_LOGGER-function block.
( S14/16 )
Selects the signal which is measured in channel 4.
604
FB_I: C4
SC: -
HL: 19999
LL: 0
D: 10504
U: -
DLOG.[IN5]
Input of DATA_LOGGER-function block.
( S14/16 )
Selects the signal which is measured in channel 5.
605
FB_I: C4
SC: -
HL: 19999
LL: 0
D: 11302
U: -
DLOG.[IN6]
Input of DATA_LOGGER-function block.
( S14/16 )
Selects the signal which is measured in channel 6.
606
FB_I: C4
SC: -
HL: 19999
LL: 0
D: 10401
U: -
DLOG.TRIGG_COND
Parameter of DATA_LOGGER-function block.
( S14/16 )
Selects the triggering condition for the data logger:
0 = EXTERNAL
1 = FAULT or EXT
2 = DIFFERENCE
3 = MAX
4 = MIN
607
FB_P: E2
SC: -
HL: 4
LL: 0
D: 1
U: -
DLOG.TRIGG_VALUE
Parameter of DATA_LOGGER-function block.
( S14/16 )
Reference value that will be used if the trigger condition DLOG.TRIGG_CONT is set to
DIFFERENCE, MAX or MIN
608
FB_P: I2
SC: -
HL: 32767
LL: -32768
D: 20000
U: -
DLOG.TRIGG_DELAY
Parameter of DATA_LOGGER-function block.
( S14/16 )
Number of samples collected after triggering instant. Length of data logger is 1000
samples in each channel.
609
FB_P: I2
SC: -
HL: 1000
LL: 0
D: 200
U: -
DLOG.SAMPL_INT
Parameter of DATA_LOGGER-function block.
( S14/16 )
Sampling interval defining how often a measurement is made in each channel.
610
FB_P: I2
SC: 1
HL: 1000
LL: 1
D: 3
U: ms