DCS500 Pin and Parameter list
A 87
MAIN_CONT_ON
Signal of DRIVE LOGIC-function block
( S3/16 )
0 = command to put main contactor in off-state
-1 = command to put main contactor in on-state.
10910
FB_O: B
SC: BO
HL: -
LL: -
D: -
U: -
TRIP_DC_BREAKER
Signal of DRIVE LOGIC-function block
( S3/16 )
0 = no command to a dc breaker
-1 = command to open the dc breaker.
10911
FB_O: B
SC: BO
HL: -
LL: -
D: -
U: -
DYN_BRAKE_ON
Signal of DRIVE LOGIC-function block
( S3/16 )
0 = no command to a dynamic brake
-1 = command to close the dynamic brake.
10912
FB_O: B
SC: BO
HL: -
LL: -
D: -
U: -
MOTOR_ACT
Signal of DRIVE LOGIC-function block
( S3/16 )
0 = parameter set for motor 1 is active
-1 = parameter set for motor 2 is active.
10913
FB_O: B
SC: BO
HL: -
LL: -
D: -
U: -
AUTO-RECLOSING
Signal of DRIVE LOGIC-function block
( S3/16 )
0 = Auto-reclosing function is not active
-1 = Auto-reclosing function is active.
10914
FB_O: B
SC: BO
HL: -
LL: -
D: -
U: -
COMM_FAULT
Signal of DRIVE LOGIC-function block
( S3/16 )
0 = there is no active communication fault in the drive
-1 = there is an active communication fault in the drive.
10915
FB_O: B
SC: BO
HL: -
LL: -
D: -
U: -
RUN_DCF
Signal of DCF FIELDMODE-function block
(S2/16 | S21.232)
Only active if DCF MODE = FEXLINK NODE1 or FEXLINK NODE2. Can be used to start
and stop a DCF 500B, if this converter is connected via FEX-LINK (X16: to X16:
connection) to a DCS 500B and no external start / stop command should be used to
control the field exciter. In this case connect this signal to input ON/OFF (901) and RUN1
(902) of the DRIVE LOGIC. The signal definition is:
0 = command to put DCF500B field exciter in off-state
-1 = command to put DCF500B field exciter in on-state
10916
FB_O: B
SC: BO
HL: -
LL: -
D: -
U: -
RESET_DCF
Signal of DCF FIELDMODE-function block
(S2/16 | S21.232)
Only active if DCF MODE = FEXLINK NODE1 or FEXLINK NODE2. Can be used to reset
faults at a DCF 500B, if this converter is connected via FEX-LINK (X16: to X16:
connection) to a DCS 500B and no external RESET command should be used to reset
faults at the field exciter. In this case connect this signal to input RESET (907) of the
DRIVE LOGIC. The signal definition is:
0 = no command to DCF500B field exciter
-1 = command to reset DCF500B field exciter faults
10917
FB_O: B
SC: BO
HL: -
LL: -
D: -
U: -
Содержание DCS 500B
Страница 8: ......
Страница 102: ...Functional Software description 94 DCS 500 Software Description ...
Страница 105: ...DCS 500 Thyristor Power converters Parameter and Signal list Software Version 21 233 Diagram S21V2_0 Appendix A ...
Страница 227: ......