DCS500 Pin and Parameter list
A 41
REV.REF_HYST
Parameter of MOTOR_1_FIELD_OPTIONS-function block.
( S8/16 )
Used in field reversal function. Hysteresis for torque reference during field reversal. The
absolute value of torque reference must be bigger than
REV.REF_HYST
before the field
reversal can take place.
1319
FB_P: I2
SC: TORQ
HL: 4000
LL: 0
D: 80
U: %
REV.FLUX_TD
Parameter of MOTOR_1_FIELD_OPTIONS-function block.
( S8/16 )
Time period during field reversal when field current and internal FLUX of the motor don’t
correspond to each other. The flag FIELD1_REV_ACK located in FEXC_STATUS
(11203) changes state after this time delay.
1320
FB_P: I2
SC: 1
HL: 20000
LL: 0
D: 0
U: ms
F1_CURR_MIN_TD
Parameter of MOTOR_1_FIELD_OPTIONS-function block.
(S8/16 | S21.233)
This parameter defines the time the actual field current is allowed to be lower than the
threshold F1_CURR_GT_MIN_L (1305) without error signal F39 (NO FIELD ACK). As
long as the actual field current is higher than the threshold, the flag FIELD1_CURR_MIN_L
located in FEXC_STATUS (11203) is set.
1321
FB_P: I2
SC: 0.01
HL: 1000
LL: 10
D: 200
U: s
Содержание DCS 500B
Страница 8: ......
Страница 102: ...Functional Software description 94 DCS 500 Software Description ...
Страница 105: ...DCS 500 Thyristor Power converters Parameter and Signal list Software Version 21 233 Diagram S21V2_0 Appendix A ...
Страница 227: ......