DCS500 Pin and Parameter list
A 108
Group 123: TORQUE and CURRENT LIMITS
SPC_TORQMAX1
Signal of TORQUE/CURRENT LIMITATION-function block.
( S6/16 )
Positive torque limit for speed controller.
12301
FB_O: I2
SC: TORQ
HL: -
LL: -
D: -
U: %
SPC_TORQMIN1
Signal of TORQUE/CURRENT LIMITATION-function block.
( S6/16 )
Negative torque limit for speed controller.
12302
FB_O: I2
SC: TORQ
HL: -
LL: -
D: -
U: %
TREF_TORQMAX1
Signal of TORQUE/CURRENT LIMITATION-function block.
( S6/16 )
Positive torque limit for torque reference chain.
12303
FB_O: I2
SC: TORQ
HL: -
LL: -
D: -
U: %
TREF_TORQMIN1
Signal of TORQUE/CURRENT LIMITATION-function block.
( S6/16 )
Negative torque limit for torque reference chain.
12304
FB_O: I2
SC: TORQ
HL: -
LL: -
D: -
U: %
TORQMAX2
Signal of TORQUE/CURRENT LIMITATION-function block.
( S6/16 )
Positive torque limit before external torque limitation.
12305
FB_O: I2
SC: TORQ
HL: -
LL: -
D: -
U: %
TORQMIN2
Signal of TORQUE/CURRENT LIMITATION-function block.
( S6/16 )
Negative torque limit before external torque limitation.
12306
FB_O: I2
SC: TORQ
HL: -
LL: -
D: -
U: %
CURR_LIM_P
Signal of TORQUE/CURRENT LIMITATION-function block.
( S6/16 )
Positive current limit for current contoller.
12307
FB_O: I2
SC:MCURR
HL: -
LL: -
D: -
U: A
CURR_LIM_N
Signal of TORQUE/CURRENT LIMITATION-function block.
( S6/16 )
Negative current limit for current contoller.
12308
FB_O: I2
SC:MCURR
HL: -
LL: -
D: -
U: A