DCS500 Pin and Parameter list
A 6
Maximum
HL = high level; is given as internal values
Minimum
LL = low level; is given as internal values
Default
is given as internal values
Unit
either the maximum or the minimum or the default value has to be multiplied
by the scaling factor; then the unit has to be added to that number to get the
physical value
Example:
The parameter which is defining nominal voltage of the motor has following
description:
U_MOTN_V
Parameter of SETTINGS-function block
(S2/16 | mod in S21.232)
The nominal voltage of the motor in volts. (higher HL in S21.232)
501
FB_P: I2
SC: 1
HL: 1800
LL: 0
D: 0
U: V
Name
U_MOTN_V
Para
will be found at the SETTINGS function block, which is shown on the
software diagrams on page 2 out of 16; this parameter has been modified at
software version S21.232 and has still this new function
Expl
description in verbal form
Index
parameter group = 5, element = 01
Data type
FB_P:
Parameter of a function block
I2
16-bit signed integer
Scaling factor
equal 1
Maximum
1800
Minimum
0
Default
0 (at C1, C2, C3: will be set by the converter automatically)
Unit
is Volt; example: HL (= 1800) * SC (= 1) = 1800V