DCS500 Pin and Parameter list
A 21
SET_CONV_TYPE
Parameter of SETTINGS-function block.
( S2/16 )
The type of the converter.
Note:
This parameter overwrites the type of the converter defined by type code resistors !
0:
(type code resistors are in use)
1:
(C1 construction type converter)
2:
(C2 construction type converter)
3
(C3 construction type converter)
4:
(C4 construction type converter)
520
FB_P: I2
SC: 1
HL: 4
LL: 0
D: 0
U: -
SET_QUADR_TYPE
Parameter of SETTINGS-function block.
( S2/16 )
The type of the converter.
Note:
This parameter overwrites the type of the converter defined by type code resistors !
0:
(type code resistors are in use)
1:
(ONE_QUADRANT type converter DCx 501)
4:
(FOUR_QUADRANT type converter DCx 502)
521
FB_P: I2
SC: 1
HL: 4
LL: 0
D: 0
U: -
LANGUAGE
Parameter of SETTINGS-function block.
( S2/16 )
Selects the language used for alarm/warning texts in the panel / CMT.
0 = ENGLISH
1 = GERMAN
2 = ITALIAN
3 = SPANISH
4 = FRENCH
522
FB_P: E2
SC: -
HL: 4
LL: 0
D: 0
U: -
CURR_ACT_FILT_TC
Parameter of SETTINGS-function block.
( S2/16 )
Filter time constant for calculated CONV_CURR_ACT (10501) and ARM_CURR_ACT
(10502).
523
FB_P: I2
SC: 1
HL: 100
LL: 0
D: 0
U: ms
PLL_CONTROL
Parameter of SETTINGS-function block.
(S2/16 | S21.230)
The network is reproduced by a software PLL system. If the frequency or the phase shift of
the network changes in comparison to the PLL, the PLL system has to be corrected. The
gain of this correction is set by this parameter.
524
FB_P: I2
SC: 1
HL: 6
LL: 1
D: 4
U: -
UNI_FILT_TC
Parameter of SETTINGS-function block
(S2/16 | S21.232)
Filter time constant to smooth the feedforward control of the firing angle based on the line
voltage signal. Line voltage variations will be compensated with a time delay.
525
FB_P: I2
SC: 1.0
HL: 10000
LL: 0
D: 10
U: ms
OFFSET_UDC
Parameter of SETTINGS-function block
(S2/16 | S21.232)
The calculated EMF signal used for speed control at the SPEED_MEASUREMENT
function block can be offset compensated with this parameter.
526
FB_P: I2
SC: 1.0
HL: 81
LL: -80
D: 0
U: -