DCS500 Pin and Parameter list
A 55
Group 22: SPEED MONITOR
MIN_SPEED_L
Parameter of SPEED_MONITOR-function block.
( S5/16 )
Limit value for minimum speed detection.
When speed is below this limit MIN_SPEED (12201) output of the function block is set.
2201
FB_P: I2
SC: SPEED
HL: 30000
LL: 0
D: 50
U: rpm
SPEED_L1
Parameter of SPEED_MONITOR-function block.
( S5/16 )
Limit value for speed level detection. When speed is above this limit SPEED_GT_L1
(12202) output of the function block is set.
2202
FB_P: I2
SC: SPEED
HL: 30000
LL: 0
D: 5000
U: rpm
SPEED_L2
Parameter of SPEED_MONITOR-function block.
( S5/16 )
Limit value for speed level detection. When speed is above this limit SPEED_GT_L2
(12203) output of the function block is set.
2203
FB_P: I2
SC: SPEED
HL: 30000
LL: 0
D: 10000
U: rpm
OVERSPEEDLIMIT
Parameter of SPEED_MONITOR-function block.
( S5/16 )
Limit value for overspeed detection. When speed is above this limit OVERSPEED (12204)
output of the function block is set an the drive will trip.
2204
FB_P: I2
SC: SPEED
HL: 30000
LL: 0
D: 23000
U: rpm
STALL.SEL
Parameter of SPEED_MONITOR-function block.
( S5/16 )
Selection parameter for stall protection:
0 = DISABLED
1 = ENABLED.
2205
FB_P: E2
SC: -
HL: 1
LL: 0
D: 0
U: -
STALL.SPEED
Parameter of SPEED_MONITOR-function block.
( S5/16 )
Speed limit value for stall detection.
When speed is below this limit and torque is higher than STALL.TORQUE for a time longer
than STALL.TIME, the drive will trip.
2206
FB_P: I2
SC: SPEED
HL: 20000
LL: 0
D: 50
U: rpm
STALL.TORQUE
Parameter of SPEED_MONITOR-function block.
( S5/16 )
Torque limit value for stall detection. Description see STALL.SPEED (2206).
2207
FB_P: I2
SC: TORQ
HL: 16000
LL: 0
D: 3000
U: %
STALL.TIME
Parameter of SPEED_MONITOR-function block.
( S5/16 )
Time delay for stall detection. Description see STALL.SPEED (2206).
2208
FB_P: I2
SC: 1
HL: 180
LL: 1
D: 10
U: s
MON.MEAS_LEV
Parameter of SPEED_MONITOR-function block.
( S5/16 )
This function is comparing speed actual from pulse or analog tacho and the calculated
EMF_ACT (10506) of the motor. If speed measurement fails the speed is zero, but the
EMF_ACT (10506) will increase when the drive is started.
MON.MEAS_LEV is the minimum absolute value the measured speed must have when
EMF_ACT (10506) is over the limit MON.EMF_V. Otherwise the drive trips to the speed
measurement fault.
2209
FB_P: I2
SC: SPEED
HL: 20000
LL: 0
D: 200
U: rpm