DCS500 Pin and Parameter list
A 86
Group 109: DRIVE LOGIC
RDY_ON
Signal of DRIVE LOGIC-function block
( S3/16 )
0 = drive is not ready for ON-command
-1 = drive is ready for ON-command.
10901
FB_O: B
SC: BO
HL: -
LL: -
D: -
U: -
RDY_RUNNING
Signal of DRIVE LOGIC-function block.
( S3/16 )
0 = drive is not ready for RUN-command
-1 = drive is ready for RUN-command.
10902
FB_O: B
SC: BO
HL: -
LL: -
D: -
U: -
RUNNING
Signal of DRIVE LOGIC-function block
( S3/16 )
0 = drive is not running
-1 = drive is running.
10903
FB_O: B
SC: BO
HL: -
LL: -
D: -
U: -
FAULT
Signal of DRIVE LOGIC-function block
( S3/16 )
0 = there is no active fault in the drive
-1 = there is an active fault in the drive.
10904
FB_O: B
SC: BO
HL: -
LL: -
D: -
U: -
ALARM
Signal of DRIVE LOGIC-function block
( S3/16 ).
0 = there is no active alarm in the drive
-1 = there is an active alarm in the drive.
10905
FB_O: B
SC: BO
HL: -
LL: -
D: -
U: -
LOCAL
Signal of DRIVE LOGIC-function block
( S3/16 )
0 = the drive is in remote control (control from I/O or via communication)
-1 = the drive is in local control (control from panel or CMT/DCS500).
10906
FB_O: B
SC: BO
HL: -
LL: -
D: -
U: -
EMESTOP_ACT
Signal of DRIVE LOGIC-function block
( S3/16 )
0 = emergency stop function is not active
-1 = emergency stop function is active.
10907
FB_O: B
SC: BO
HL: -
LL: -
D: -
U: -
FAN_ON
Signal of DRIVE LOGIC-function block
( S3/16 )
0 = command to put all fans in off-state
-1 = command to put all fans in on-state.
10908
FB_O: B
SC: BO
HL: -
LL: -
D: -
U: -
FIELD_ON
Signal of DRIVE LOGIC-function block
( S3/16 )
0 = command to put external field exciter in off-state
-1 = command to put external field exciter in on-state.
10909
FB_O: B
SC: BO
HL: -
LL: -
D: -
U: -