A 79
Group 104: CURRENT CONTROL
ARM_ALPHA
Signal of CURRENT CONTROL-function block
( S7/16 ).
Firing angle.
10401
FB_O: I2
SC: 1
HL: -
LL: -
D: -
U: -.
ARM_DIR
Signal of CURRENT CONTROL-function block
( S7/16 ).
Identification of the bridge currently in use:
0 = NO BRIDGE
1 = MOTOR BRIDGE
2 = GENERATOR BRIDGE
10402
FB_O: E2
SC: -
HL: -
LL: -
D: -
U: -
CURR_REF_IN_LIM
Signal of CURRENT CONTROL-function block
( S7/16 ).
Status signal indicating that the current reference is in limit:
0 = current reference is not in limit
-1 = current reference is in limit.
10403
FB_O: B
SC: BO
HL: -
LL: -
D: -
U: -
CURR_DER_IN_LIM
Signal of CURRENT CONTROL-function block
( S7/16 ).
Status signal indicating that the rate of change of the current reference is too high:
0 = current reference is not in limit
-1 = rate of change of current reference is in limit.
10404
FB_O: B
SC: BO
HL: -
LL: -
D: -
U: -
ARM_CURR_REF
Signal of CURRENT CONTROL-function block
( S7/16 ).
Either current or torque reference is use depending on value of REF_TYPE_SEL (405).
10405
FB_O: I2
SC: MCURR HL: -
LL: -
D: -
U: A