DCS500 Pin and Parameter list
A 51
SOFTPOT.[ENABLE]
Input of SOFT_POT-function block.
(S4/16 | S21.233)
In default condition the output of the SOFT_POT function block is reset to zero, if the drive
is stopped by removing the RUN command from the binary input. In case this behaviour is
not useful change the interconnection to a different signal. Definition of this input:
The output SOFT_POT:OUT (11904) is kept to logic level = 0 as long as this input is not
connected or the connected signal (default: RUNNING (10903)) has logic level = 0. If the
connected signal is set to logic level = -1 the function is enabled.
1923
FB_I: C4
SC: BI
HL: 19999
LL: 0
D: 10903
U: -