DCS500 Pin and Parameter list
A 39
Group 13: MOTOR 1 FIELD
[F1_REF]
Input of MOTOR_1_FIELD-function block.
( S8/16 )
Field current reference for motor 1 field exciter.
1301
FB_I: C4
SC: FCURR
HL: 19999
LL: 0
D: 11003
U: -
[F1_FORCE_FWD]
Input of MOTOR_1_FIELD-function block.
( S8/16 )
Command to force motor field in forward direction.
1302
FB_I: C4
SC: BI
HL: 19999
LL: 0
D: 0
U: -
[F1_FORCE_REV]
Input of MOTOR_1_FIELD-function block.
( S8/16 )
Command to force motor field in reverse direction.
1303
FB_I: C4
SC: BI
HL: 19999
LL: 0
D: 0
U: -
[F1_ACK]
Input of MOTOR_1_FIELD-function block.
( S8/16 )
Input for analog or digital acknowledge signal from external field excitation system.
1304
FB_I: C4
SC: -
HL: 19999
LL: 0
D: 0
U: -
F1_CURR_GT_MIN_L
Parameter of MOTOR_1_FIELD-function block.
( S8/16 )
Tripping level of minimum field current monitoring function.
When field weakening function is used, this limit must be low enough to prevent minimum
field faults at high speed!
1305
FB_P: I2
SC: FCURR
HL: 4095
LL: 0
D: 2047
U: A
F1_OVERCURR_L
Parameter of MOTOR_1_FIELD-function block.
( S8/16 )
Field overcurrent limit for motor 1. The default limit is 115% of nominal field current.
1306
FB_P: I2
SC: FCURR
HL: 8191
LL: 0
D: 4710
U: A
F1_CURR_TC
Parameter of MOTOR_1_FIELD-function block
(S8/16 ).
Filter time constant for actual field current measurement. (lower HL in S21.232)
1307
FB_P: I2
SC: 0.01
HL: 1000
LL: 0
D: 0
U: s
F1_KP
Parameter of MOTOR_1_FIELD-function block.
( S8/16 )
Proportional gain for PI controller in the field excitation unit .
1308
FB_P: I2
SC: -
HL: 4096
LL: 0
D: 1
U: -
F1_KI
Parameter of MOTOR_1_FIELD-function block.
( S8/16 )
Integral action time for PI controller in the field excitation unit .
1309
FB_P: I2
SC: 0.01
HL: 4096
LL: 0
D: 20
U: s
F1_U_AC_DIFF_MAX
Parameter of MOTOR_1_FIELD_OPTIONS-function block
(S8/16 ).
Threshold level for free-wheeling function. If two successive AC voltage measurements in
field exciter differ more than this then the 2 phase field exciter activates the free-wheeling
function. (lower HL in S21.232)
1310
FB_P: I2
SC: 1.0
HL: 1000
LL: 0
D: 10
U: %