DCS500 Pin and Parameter list
A 45
Group 16: MOTOR 2 PROTECT.
MOT2.[TEMP_IN]
Input of MOTOR_2_PROTECTION-function block.
( S9/16 )
Input where temperature measurement is connected.
1601
FB_I: C4
SC: -
HL: 19999
LL: 0
D: 0
U: -
MOT2.TEMP_ALARM_L
Parameter of MOTOR_2_PROTECTION-function block.
( S9/16 )
Motor overtemperature alarm is activated when measured temperature (PT100) or
resistance value (PTC) exceeds this limit
1602
FB_P: I2
SC: 1
HL: 4000
LL: -10
D: 0
U: C
MOT2.TEMP_FAULT_L
Parameter of MOTOR_2_PROTECTION-function block.
( S9/16 )
Motor overtemperature fault is activated and the drive will trip when measured temperature
(PT100) or resistance value (PTC) exceeds this limit
1603
FB_P: I2
SC: 1
HL: 4000
LL: -10
D: 0
U: C
MODEL2.SEL
Parameter of MOTOR_2_PROTECTION-function block.
( S9/16 )
Used to activate the temperature model for motor 2. The model will estimate the
temperature of the motor based on motor current and given model parameters.
0 = DISABLED
1 = ENABLED.
1604
FB_P: E2
SC: -
HL: 1
LL: 0
D: 0
U: -
MODEL2.CURR
Parameter of MOTOR_2_PROTECTION-function block.
( S9/16 )
Nominal current parameter for thermal model. When motor current is MODEL2.CURR
and after a time of about 5 times MODEL2.TC, the output of thermal model will be 100.
1605
FB_P: I2
SC: MCURR HL: 10000
LL: 0
D: 4096
U: A
MODEL2.ALARM_L
Parameter of MOTOR_2_PROTECTION-function block.
( S9/16 )
Motor overtemperature alarm is activated when calculated temperature exceeds this limit.
1606
FB_P: I2
SC: 1
HL: 130
LL: 10
D: 120
U: %
MODEL2.TRIP_L
Parameter of MOTOR_2_PROTECTION-function block.
( S9/16 )
Motor overtemperature fault is activated and the drive will trip when calculated temperature
exceeds this limit.
1607
FB_P: I2
SC: 1
HL: 130
LL: 10
D: 130
U: %
MODEL2.TC
Parameter of MOTOR_2_PROTECTION-function block.
( S9/16 )
Thermal time constant parameter for thermal model. The time in which the temperature
rises to 63% of the nominal value. When motor current is MODEL2.CURR and after a
time of about 5 times MODEL2.TC, the output of thermal model will be 100.
1608
FB_P: I2
SC: 1
HL: 5400
LL: 0
D: 240
U: s