Fault tracing
279
0009
MOT OVERTEMP
(4310)
bit 8
(programmable fault
function
/
)
Motor temperature is too high
(or appears to be too high) due
to excessive load, insufficient
motor power, inadequate
cooling or incorrect start-up
data.
Check motor ratings, load and cooling.
Check start-up data.
Check fault function parameters.
Measured motor temperature
has exceeded fault limit set by
parameter
FAULT LIMIT.
Check value of fault limit.
Check that actual number of sensors corresponds to
value set by parameter (
SENSOR TYPE).
Let motor cool down. Ensure proper motor cooling:
Check cooling fan, clean cooling surfaces, etc.
0010
PANEL LOSS
(5300)
bit 9
(programmable fault
function
Control panel selected as active
control location for drive has
ceased communicating.
Check panel connection.
Check fault function parameters.
Check control panel connector.
Refit control panel in mounting platform.
If drive is external control mode (REM) and is set to
accept start/stop, direction commands or references
via control panel:
Check group
settings.
0011
ID RUN FAIL
(FF84)
bit 10
Motor ID Run is not completed
successfully.
Check motor connection.
Check start-up data (group
Check maximum speed (parameter
). It should
be at least 80% of motor nominal speed (parameter
).
Ensure ID run has been performed according to
instructions in section
page
.
0012
MOTOR STALL
(7121)
bit 11
(programmable fault
function
)
Motor is operating in stall region
due to e.g. excessive load or
insufficient motor power.
Check motor load and drive ratings.
Check fault function parameters.
0014
EXT FAULT 1
(9000)
bit 13
(programmable
fault function
External fault 1
Check external devices for faults.
Check parameter
EXTERNAL FAULT 1 setting.
0015
EXT FAULT 2
(9001)
bit 14
(programmable
fault function
External fault 2
Check external devices for faults.
Check parameter
EXTERNAL FAULT 2 setting.
0016
EARTH FAULT
(2330)
bit 15
(programmable fault
function
Drive has detected earth
(ground) fault in motor or motor
cable.
Check motor.
Check fault function parameters.
Check motor cable. Motor cable length must not
exceed maximum specifications. See section
.
CODE
FAULT
CAUSE
WHAT TO DO
Содержание ACS350 Series
Страница 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Страница 4: ......
Страница 8: ...Safety 8 ...
Страница 18: ...Table of contents 18 ...
Страница 24: ...Hardware description 24 ...
Страница 44: ...Installation checklist 44 ...
Страница 56: ...Start up control with I O and ID Run 56 ...
Страница 140: ...Program features 140 ...
Страница 242: ...Actual signals and parameters 242 ...
Страница 266: ...Fieldbus control with embedded fieldbus 266 ...
Страница 284: ...Fault tracing 284 ...
Страница 288: ...Maintenance and hardware diagnostics 288 ...
Страница 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Страница 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Страница 312: ...Dimensions 312 Frame size R4 IP20 cabinet installation UL open Frame size R4 cabinet installation UL open 3AFE68935644 ...
Страница 313: ......