A diagram of the cable routing is shown below.
Control cable ducts
90 °
min. 500 mm (20 in.)
Motor cable
Input power cable
Control cables
min. 200 mm (8 in.)
min. 300 mm (12 in.)
Motor cable
Power cable
Drive
230 V
24 V
24 V 230 V
Lead 24 V and 230 V control cables in
separate ducts inside the cabinet.
Not allowed unless the 24 V cable is
insulated for 230 V or insulated with an
insulation sleeving for 230 V.