Actual signals and parameters
149
1502
AO1 CONTENT MIN
Defines the minimum value for signal selected with parameter
1501 AO1 CONTENT SEL.
-
1503
AO1 CONTENT MAX
Defines the maximum value for signal selected with parameter
1501 AO1 CONTENT SEL.
-
1504
MINIMUM AO1
Defines the minimum value for the analog output signal AO.
0
1505
MAXIMUM AO1
Defines the maximum value for the analog output signal AO.
20
1506
FILTER AO1
Defines the filter time constant for analog output AO, i.e the time
within 63% of a step change is reached.
0.1
16
SYSTEM CONTROLS
Run Enable, parameter lock etc.
1601
RUN ENABLE
Selects a source for the external Run Enable signal.
NOT SEL
1602
PARAMETER LOCK
Selects the state of the parameter lock.
OPEN
1603
PASS CODE
Selects the pass code for the parameter lock.
0
1604
FAULT RESET SEL
Selects the source for the fault reset signal.
KEYPAD
1605
USER PAR SET CHG
Enables the change of the User Parameter Set through a digital
input.
NOT SEL
1606
LOCAL LOCK
Disables entering local control mode or selects the source for the
local control mode lock signal.
NOT SEL
1607
PARAM SAVE
Saves the valid parameter values to the permanent memory.
DONE
1608
START ENABLE 1
Selects the source for the Start Enable 1 signal.
NOT SEL
1609
START ENABLE 2
Selects the source for the Start Enable 2 signal.
NOT SEL
1610
DISPLAY ALARMS
Activates/deactivates alarms.
NO
1611
PARAMETER VIEW
Selects the parameter view, i.e which parameters are shown.
DEFAULT
18
FREQ IN & TRAN OUT Frequency input and transistor output signal processing.
1801
FREQ INPUT MIN
Defines the minimum input value when DI5 is used as a
frequency input.
0
1802
FREQ INPUT MAX
Defines the maximum input value when DI5 is used as a
frequency input.
1000
1803
FILTER FREQ IN
Defines the filter time constant for frequency input.
0.1
1804
TO MODE
Selects the operation mode for the transistor output TO.
DIGITAL
1805
DO SIGNAL
Selects a drive status indicated through digital output DO.
FAULT(-1)
1806
DO ON DELAY
Defines the operation delay for digital output DO.
0
1807
DO OFF DELAY
Defines the release delay for digital output DO.
0
1808
FO CONTENT SEL
Selects a drive signal to be connected to frequency output FO.
104
1809
FO CONTENT MIN
Defines the minimum frequency output FO signal value.
-
1810
FO CONTENT MAX
Defines the maximum frequency output FO signal value.
-
1811
MINIMUM FO
Defines the minimum value for frequency output FO.
10
1812
MAXIMUM FO
Defines the maximum value for frequency output FO.
1000
1813
FILTER FO
Defines the filter time constant for frequency output FO.
0.1
19
TIMER & COUNTER
Timer and counter for start and stop control
1901
TIMER DELAY
Defines the time delay for the timer.
10
1902
TIMER START
Selects the source for the timer start signal.
NOT SEL
1903
TIMER RESET
Selects the source for the timer reset signal.
NOT SEL
1904
COUNTER ENABLE
Selects the source for the counter enable signal.
DISABLED
1905
COUNTER LIMIT
Defines the counter limit.
1000
1906
COUNTER INPUT
Selects the input signal source for the counter.
PLS IN(DI5)
1907
COUNTER RESET
Selects the source for the counter reset signal.
NOT SEL
1908
COUNTER RES VAL
Defines the value for the counter after reset.
0
1909
COUNT DIVIDER
Defines the divider for the pulse counter.
0
1910
COUNT DIRECTION
Defines the source for the counter direction selection.
UP
1911
CNTR S/S COMMAND Selects the source for the drive start/stop command when
parameter 1001 EXT1 COMMANDS value is set to COUNTER
START / COUNTER STOP.
NOT SEL
Parameters – short form list
Index
Name/Selection
Description
Def
Custom
Содержание ACS350 Series
Страница 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Страница 4: ......
Страница 8: ...Safety 8 ...
Страница 18: ...Table of contents 18 ...
Страница 24: ...Hardware description 24 ...
Страница 44: ...Installation checklist 44 ...
Страница 56: ...Start up control with I O and ID Run 56 ...
Страница 140: ...Program features 140 ...
Страница 242: ...Actual signals and parameters 242 ...
Страница 266: ...Fieldbus control with embedded fieldbus 266 ...
Страница 284: ...Fault tracing 284 ...
Страница 288: ...Maintenance and hardware diagnostics 288 ...
Страница 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Страница 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Страница 312: ...Dimensions 312 Frame size R4 IP20 cabinet installation UL open Frame size R4 cabinet installation UL open 3AFE68935644 ...
Страница 313: ......