Actual signals and parameters
178
ENABLED
Counter enabled
6
1905
COUNTER LIMIT
Defines the counter limit.
1000
0…65535
Limit value
1 = 1
1906
COUNTER INPUT
Selects the input signal source for the counter.
PLS IN(DI5)
PLS IN(DI 5)
Digital input DI5 pulses. When a pulse is detected, the counter value
increases by 1.
1
ENC W/O DIR
Encoder pulse edges. When a rising or a falling edge is detected, the counter
value increases by 1.
2
ENC WITH DIR
Encoder pulse edges. The direction of rotation is taken into account. When
a rising or a falling edge is detected and the direction of rotation is forward,
the counter value increases by 1. When the direction of rotation is reverse,
the counter value decreases by 1.
3
FILTERED DI5
Filtered digital input DI5 pulses. When a pulse is detected, the counter value
increases by 1.
Note:
Due to filtering, the maximum input signal frequency is 50 Hz.
4
1907
COUNTER RESET
Selects the source for the counter reset signal.
NOT SEL
DI1(INV)
Counter reset through inverted digital input DI1. 0 = active, 1 = inactive.
-1
DI2(INV)
See selection DI1(INV).
-2
DI3(INV)
See selection DI1(INV).
-3
DI4(INV)
See selection DI1(INV).
-4
DI5(INV)
See selection DI1(INV).
-5
NOT SEL
No reset signal
0
DI1
Counter reset through digital input DI1. 1 = active, 0 = inactive.
1
DI2
See selection DI1.
2
DI3
See selection DI1.
3
DI4
See selection DI1.
4
DI5
See selection DI1.
5
AT LIMIT
Reset at the limit defined by parameter
COUNTER LIMIT
6
STRT/STP CMD
Counter reset at start/stop command. Source for the start/stop is selected by
parameter
7
S/S CMD(INV)
Counter reset at start/stop command (inverted), i.e. counter is reset when
start/stop command is deactivated. Start signal source is selected by
parameter
TIMER START.
8
RESET
Reset enabled
9
1908
COUNTER RES VAL
Defines the value for the counter after reset.
0
0…65535
Counter value
1 = 1
1909
COUNT DIVIDER
Defines the divider for the pulse counter.
0
0…12
Pulse counter divider N. Every 2
N
bit is counted.
1 = 1
1910
COUNT DIRECTION
Defines the source for the counter direction selection.
UP
DI1(INV)
Counter direction selection through inverted digital input DI1. 1 = counts up,
0 = counts down.
-1
DI2(INV)
See selection DI1(INV).
-2
DI3(INV)
See selection DI1(INV).
-3
DI4(INV)
See selection DI1(INV).
-4
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
Содержание ACS350 Series
Страница 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Страница 4: ......
Страница 8: ...Safety 8 ...
Страница 18: ...Table of contents 18 ...
Страница 24: ...Hardware description 24 ...
Страница 44: ...Installation checklist 44 ...
Страница 56: ...Start up control with I O and ID Run 56 ...
Страница 140: ...Program features 140 ...
Страница 242: ...Actual signals and parameters 242 ...
Страница 266: ...Fieldbus control with embedded fieldbus 266 ...
Страница 284: ...Fault tracing 284 ...
Страница 288: ...Maintenance and hardware diagnostics 288 ...
Страница 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Страница 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Страница 312: ...Dimensions 312 Frame size R4 IP20 cabinet installation UL open Frame size R4 cabinet installation UL open 3AFE68935644 ...
Страница 313: ......