Actual signals and parameters
172
DI3
See selection DI1.
3
DI4
See selection DI1.
4
DI5
See selection DI1.
5
START/STOP
Reset along with the stop signal received through a digital input, or by control
panel.
Note:
Do not use this option when start, stop and direction commands are
received through fieldbus communication.
7
COMM
Fieldbus interface as the source for the fault reset signal, i.e. control word
FB CMD WORD 1 bit 4 (with ABB drives profile
EFB PAR 19
bit 7). The control word is sent by the fieldbus controller via the fieldbus
adapter or embedded fieldbus (modbus) to the drive. For the control word
bits, see sections
on page
on page
.
8
DI1(INV)
Reset through inverted digital input DI1 (reset by a falling edge of DI1) or by
control panel
-1
DI2(INV)
See selection DI1(INV).
-2
DI3(INV)
See selection DI1(INV).
-3
DI4(INV)
See selection DI1(INV).
-4
DI5(INV)
See selection DI1(INV).
-5
1605
USER PAR SET CHG Enables the change of the User Parameter Set through a digital input. See
parameter
APPLIC MACRO. The change is only allowed when the
drive is stopped. During the change, the drive will not start.
Note:
Always save the User Parameter Set by parameter
after
changing any parameter setting, or reperforming the motor identification. The
last settings saved by the user are loaded into use whenever the power is
switched off and on again or the parameter 9902 setting is changed. Any
unsaved changes will be lost.
Note:
The value of this parameter is not included in the User Parameter Sets.
A setting once made remains despite User Parameter Set change.
Note:
Selection of User Parameter Set 2 can be supervised via relay output
RELAY OUTPUT 1.
NOT SEL
NOT SEL
User Parameter Set change is not possible through a digital input. Parameter
Sets can be changed only from control panel.
0
DI1
User Parameter Set control through digital input DI1. Falling edge of digital
input DI1: User Parameter Set 1 is loaded into use. Rising edge of digital
input DI1: User Parameter Set 2 is loaded into use.
1
DI2
See selection DI1.
2
DI3
See selection DI1.
3
DI4
See selection DI1.
4
DI5
See selection DI1.
5
DI1,2
User Parameter Set selection through digital inputs DI1 and DI2. 1 = DI
active, 0 = DI inactive.
7
DI2,3
See selection DI1,2.
8
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
DI1
DI2 User Parameter Set
0
0
User Parameter Set 1
1
0
User Parameter Set 2
0
1
User Parameter Set 3
Содержание ACS350 Series
Страница 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Страница 4: ......
Страница 8: ...Safety 8 ...
Страница 18: ...Table of contents 18 ...
Страница 24: ...Hardware description 24 ...
Страница 44: ...Installation checklist 44 ...
Страница 56: ...Start up control with I O and ID Run 56 ...
Страница 140: ...Program features 140 ...
Страница 242: ...Actual signals and parameters 242 ...
Страница 266: ...Fieldbus control with embedded fieldbus 266 ...
Страница 284: ...Fault tracing 284 ...
Страница 288: ...Maintenance and hardware diagnostics 288 ...
Страница 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Страница 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Страница 312: ...Dimensions 312 Frame size R4 IP20 cabinet installation UL open Frame size R4 cabinet installation UL open 3AFE68935644 ...
Страница 313: ......