Program features
115
Scalar control
It is possible to select scalar control as the motor control method instead of vector
control. In the scalar control mode, the drive is controlled with a frequency reference.
It is recommended to activate the scalar control mode in the following special
applications:
• In multimotor drives: 1) if the load is not equally shared between the motors,
2) if the motors are of different sizes, or 3) if the motors are going to be changed
after the motor identification.
• If the nominal current of the motor is less than 20% of the nominal output current
of the drive.
In the scalar control mode, some standard features are not available.
Settings
Parameter
MOTOR CTRL MODE
IR compensation for a scalar controlled drive
IR compensation is active only when the motor
control mode is scalar (see section
). When IR compensation is
activated, the drive gives an extra voltage boost
to the motor at low speeds. IR compensation is
useful in applications that require high breakaway
torque. In vector control, no IR compensation is
possible/needed.
Settings
Parameter
IR COMP VOLT
Programmable protection functions
AI<Min
AI<Min function defines the drive operation if an analog input signal falls below the
set minimum limit.
Settings
Parameters
AI<MIN FUNCTION,
AI1 FAULT LIMIT and
AI2 FAULT
LIMIT
Panel Loss
Panel Loss function defines the operation of the drive if the control panel selected as
control location for the drive stops communicating.
Settings
Parameter
PANEL COMM ERR
f
(Hz)
Motor voltage
No compensation
IR compensation
Содержание ACS350 Series
Страница 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Страница 4: ......
Страница 8: ...Safety 8 ...
Страница 18: ...Table of contents 18 ...
Страница 24: ...Hardware description 24 ...
Страница 44: ...Installation checklist 44 ...
Страница 56: ...Start up control with I O and ID Run 56 ...
Страница 140: ...Program features 140 ...
Страница 242: ...Actual signals and parameters 242 ...
Страница 266: ...Fieldbus control with embedded fieldbus 266 ...
Страница 284: ...Fault tracing 284 ...
Страница 288: ...Maintenance and hardware diagnostics 288 ...
Страница 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Страница 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Страница 312: ...Dimensions 312 Frame size R4 IP20 cabinet installation UL open Frame size R4 cabinet installation UL open 3AFE68935644 ...
Страница 313: ......