Program features
111
Constant speeds
It is possible to define seven positive constant speeds. Constant speeds are
selected with digital inputs. Constant speed activation overrides the external speed
reference.
Constant speed selections are ignored if
• torque control is active, or
• PID reference is being followed, or
• drive is in local control mode.
This function operates on a 2 ms time level.
Settings
Parameter group
Constant speed 7 (
CONST SPEED 7) is also used for fault functions. See
parameter group
Constant speed 6 or 7 (
CONST SPEED 6 /
CONST SPEED 7) is also
used for jogging function. See section
.