Application macros
87
ABB Standard macro
This is the default macro. It provides a general purpose I/O configuration with three
constant speeds. Parameter values are the default values given in chapter
, starting from page
If you use other than the default connections presented below, see section
on page
.
Default I/O connections
max. 500 ohm
1…10 kohm
X1A
1
SCR
Signal cable shield (screen)
2
AI1
Output frequency reference
: 0…10 V
1)
3
GND
Analog input circuit common
4
+10V
Reference voltage: +10 VDC, max. 10 mA
5
AI2
Not in use by default. 0…10 V
6
GND
Analog input circuit common
7
AO
Output frequency value
: 0…20 mA
8
GND
Analog output circuit common
9
+24V
Auxiliary voltage output: +24 VDC, max. 200 mA
10
GND
Auxiliary voltage output common
11
DCOM
Digital input common
12
DI1
Stop (0) / Start (1)
13
DI2
Forward (0) / Reverse (1)
14
DI3
Constant speed selection
2)
15
DI4
Constant speed selection
2)
16
DI5
Acceleration and deceleration selection
3)
X1B
17
ROCOM
Relay output
No fault [Fault (-1)]
18
RONC
19
RONO
20
DOSRC
Digital output, max. 100 mA
No fault [Fault (-1)]
21
DOOUT
22
DOGND
4)
1)
AI1 is used as a speed reference if vector mode
is selected.
2)
:
3)
0 = ramp times according to parameters
and
1 = ramp times according to parameters
and
4)
360 degree grounding under a clamp.
Tightening torque = 0.5 N·m / 4.4 lbf. in.
DI3 DI4 Operation (parameter)
0
0 Set speed through AI1
1
0 Speed 1 (
0
1 Speed 2 (
1
1 Speed 3 (
Содержание ACS350 Series
Страница 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Страница 4: ......
Страница 8: ...Safety 8 ...
Страница 18: ...Table of contents 18 ...
Страница 24: ...Hardware description 24 ...
Страница 44: ...Installation checklist 44 ...
Страница 56: ...Start up control with I O and ID Run 56 ...
Страница 140: ...Program features 140 ...
Страница 242: ...Actual signals and parameters 242 ...
Страница 266: ...Fieldbus control with embedded fieldbus 266 ...
Страница 284: ...Fault tracing 284 ...
Страница 288: ...Maintenance and hardware diagnostics 288 ...
Страница 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Страница 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Страница 312: ...Dimensions 312 Frame size R4 IP20 cabinet installation UL open Frame size R4 cabinet installation UL open 3AFE68935644 ...
Страница 313: ......