Planning electrical installation
32
Selecting the power cables
General rules
Dimension the input power and motor cables
according to local regulations
.
• The cable must be able to carry the drive load current. See chapter
for the rated currents.
• The cable must be rated for at least 70
°
C maximum permissible temperature of
the conductor in continuous use. For US, see section
on page
• The conductivity of the PE conductor must be equal to that of the phase
conductor (same cross-sectional area).
• 600 VAC cable is accepted for up to 500 VAC.
• Refer to chapter
for the EMC requirements.
A symmetrical shielded motor cable (see the figure below) must be used to meet the
EMC requirements of the CE and C-tick marks.
A four-conductor system is allowed for input cabling, but a shielded symmetrical
cable is recommended.
Compared to a four-conductor system, the use of a symmetrical shielded cable
reduces electromagnetic emission of the whole drive system as well as motor
bearing currents and wear.
Alternative power cable types
Power cable types that can be used with the drive are presented below.
Symmetrical shielded cable: three phase conductors,
a concentric or otherwise symmetrically constructed
PE conductor and a shield
Motor cables
(recommended for input cables also)
PE conductor
and shield
Shield
Shield
PE
PE
Allowed as input cables
A four-conductor system: three phase conductors and
a protective conductor
Note:
A separate PE conductor is required if the
conductivity of the cable shield is not sufficient for the
purpose.
Shield
PE
PE
Содержание ACS350 Series
Страница 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Страница 4: ......
Страница 8: ...Safety 8 ...
Страница 18: ...Table of contents 18 ...
Страница 24: ...Hardware description 24 ...
Страница 44: ...Installation checklist 44 ...
Страница 56: ...Start up control with I O and ID Run 56 ...
Страница 140: ...Program features 140 ...
Страница 242: ...Actual signals and parameters 242 ...
Страница 266: ...Fieldbus control with embedded fieldbus 266 ...
Страница 284: ...Fault tracing 284 ...
Страница 288: ...Maintenance and hardware diagnostics 288 ...
Страница 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Страница 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Страница 312: ...Dimensions 312 Frame size R4 IP20 cabinet installation UL open Frame size R4 cabinet installation UL open 3AFE68935644 ...
Страница 313: ......