The following table gives information on the contents of the modbus addresses
40001...40012 and 40031...40034.
Note:
Parameter writes through standard Modbus are always volatile i.e. modified
values are not automatically stored to permanent memory. Use parameter
PARAM SAVE to save all changed values.
Modbus register
Access
Information
40001 Control Word
R/W
Control Word. Supported only by ABB Drives profile, i.e.
when
EFB CTRL PROFILE setting is ABB DRV LIM or
ABB DRV FULL. Parameter
EFB PAR 19 shows a
copy of the Control Word in hexadecimal format.
40002 Reference 1
R/W
External reference REF1. See section
on page
40003 Reference 2
R/W
External reference REF2. See section
on page
40004 Status Word
R
Status Word. Supported only by ABB Drives profile, when
EFB CTRL PROFILE setting is ABB DRV LIM or ABB
EFB PAR 20 shows a copy of
the Control Word in hexadecimal format.
40005
...
40012
Actual 1...8
R
Actual value 1...8. Use parameter
...
to selects an
actual value to be mapped to modbus register
40005...40012.
40031 Control Word LSW
R/W
FB CMD WORD 1, i.e. the least significant word of the
DCU profile 32-bit Control Word.
Supported only by DCU profile, i.e. when
EFB CTRL
PROFILE setting is DCU PROFILE.
40032 Control Word MSW
R/W
FB CMD WORD 2, i.e. the most significant word of the
DCU profile 32-bit Control Word.
Supported only by DCU profile, i.e. when
EFB CTRL
PROFILE setting is DCU PROFILE.
40033 Status Word LSW
R
FB STS WORD 1, i.e. the least significant word of the
DCU profile 32-bit Status Word.
Supported only by DCU profile, i.e. when
EFB CTRL
PROFILE setting is DCU PROFILE.
40034 ACS350 STATUS
WORD MSW
R
FB STS WORD 2, i.e. the most significant word of the
DCU profile 32-bit Status Word.
Supported only by DCU profile, i.e. when
EFB CTRL
PROFILE setting is DCU PROFILE.
Содержание ACS350 Series
Страница 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Страница 4: ......
Страница 8: ...Safety 8 ...
Страница 18: ...Table of contents 18 ...
Страница 24: ...Hardware description 24 ...
Страница 44: ...Installation checklist 44 ...
Страница 56: ...Start up control with I O and ID Run 56 ...
Страница 140: ...Program features 140 ...
Страница 242: ...Actual signals and parameters 242 ...
Страница 266: ...Fieldbus control with embedded fieldbus 266 ...
Страница 284: ...Fault tracing 284 ...
Страница 288: ...Maintenance and hardware diagnostics 288 ...
Страница 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Страница 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Страница 312: ...Dimensions 312 Frame size R4 IP20 cabinet installation UL open Frame size R4 cabinet installation UL open 3AFE68935644 ...
Страница 313: ......