Actual signals and parameters
181
2007
MINIMUM FREQ
Defines the minimum limit for the drive output frequency.
A positive (or zero) minimum frequency value defines two ranges, one
positive and one negative.
A negative minimum frequency value defines one speed range.
Note:
MINIMUM FREQ < MAXIMUM FREQ.
0
-500.0…500.0 Hz
Minimum frequency
1 = 0.1 Hz
2008
MAXIMUM FREQ
Defines the maximum limit for the drive output frequency.
Eur: 50 /
US: 60
0.0…500.0 Hz
Maximum frequency
1 = 0.1 Hz
2013
MIN TORQUE SEL
Selects the minimum torque limit for the drive.
MIN
TORQUE 1
MIN TORQUE 1
Value defined by parameter
MIN TORQUE 1
0
DI1
Digital input DI1. 0 = parameter
MIN TORQUE 1 value. 1 = parameter
MIN TORQUE 2 value.
1
DI2
See selection DI1.
2
DI3
See selection DI1.
3
DI4
See selection DI1.
4
DI5
See selection DI1.
5
COMM
Fieldbus interface as the source for the torque limit 1/2 selection, i.e. control
word
FB CMD WORD 1 bit 15. The control word is sent by the fieldbus
controller via the fieldbus adapter or embedded fieldbus (modbus) to the
drive. For the control word bits, see section
on
Minimum torque limit 1 is defined by parameter
MIN TORQUE 1 and
minimum torque limit 2 is defined by parameter
MIN TORQUE 2.
Note:
This setting applies only for the DCU profile!
7
DI1(INV)
Inverted digital input DI1. 1 = value of parameter
MIN TORQUE 1. 0 =
MIN TORQUE 2.
-1
DI2(INV)
See selection DI1(INV).
-2
DI3(INV)
See selection DI1(INV).
-3
DI4(INV)
See selection DI1(INV).
-4
DI5(INV)
See selection DI1(INV).
-5
2014
MAX TORQUE SEL
Selects the maximum torque limit for the drive.
MAX
TORQUE 1
MAX TORQUE 1
Value of parameter
MAX TORQUE 1
DI1
Digital input DI1. 0 = parameter
MAX TORQUE 1 value. 1 = parameter
1
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
2007
2008
f
-(2007)
-(2008)
2008
2007
Allowed frequency range
Allowed frequency range
Allowed frequency range
t
f
t
2007 value is > 0
0
0
2007 value is < 0
Содержание ACS350 Series
Страница 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Страница 4: ......
Страница 8: ...Safety 8 ...
Страница 18: ...Table of contents 18 ...
Страница 24: ...Hardware description 24 ...
Страница 44: ...Installation checklist 44 ...
Страница 56: ...Start up control with I O and ID Run 56 ...
Страница 140: ...Program features 140 ...
Страница 242: ...Actual signals and parameters 242 ...
Страница 266: ...Fieldbus control with embedded fieldbus 266 ...
Страница 284: ...Fault tracing 284 ...
Страница 288: ...Maintenance and hardware diagnostics 288 ...
Страница 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Страница 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Страница 312: ...Dimensions 312 Frame size R4 IP20 cabinet installation UL open Frame size R4 cabinet installation UL open 3AFE68935644 ...
Страница 313: ......