Actual signals and parameters
150
20
LIMITS
Drive operation limits.
2001
MINIMUM SPEED
Defines the allowed minimum speed.
0
2002
MAXIMUM SPEED
Defines the allowed maximum speed.
Eur: 1500 / US:
1800
2003
MAX CURRENT
Defines the allowed maximum motor current.
1.8 ² I2N
2005
OVERVOLT CTRL
Activates or deactivates the overvoltage control of the
intermediate DC link.
ENABLE
2006
UNDERVOLT CTRL
Activates or deactivates the undervoltage control of the
intermediate DC link.
ENABLE(TIME)
2007
MINIMUM FREQ
Defines the minimum limit for the drive output frequency.
0
2008
MAXIMUM FREQ
Defines the maximum limit for the drive output frequency.
Eur: 50 / US: 60
2013
MIN TORQUE SEL
Selects the minimum torque limit for the drive.
MIN TORQUE 1
2014
MAX TORQUE SEL
Selects the maximum torque limit for the drive.
MAX TORQUE 1
2015
MIN TORQUE 1
Defines minimum torque limit 1 for the drive.
-300
2016
MIN TORQUE 2
Defines minimum torque limit 2 for the drive.
-300
2017
MAX TORQUE 1
Defines maximum torque limit 1 for the drive.
300
2018
MAX TORQUE 2
Defines maximum torque limit 2 for the drive.
300
2019
BRAKE CHOPPER
Phased out parameter in sw version 2.51b and later.
2020
BRAKE CHOPPER
Selects the brake chopper control.
INBUILT
21
START/STOP
Start and stop modes of the motor
2101
START FUNCTION
Selects the motor starting method.
AUTO
2102
STOP FUNCTION
Selects the motor stop function.
COAST
2103
DC MAGN TIME
Defines the pre-magnetising time.
0.3
2104
DC HOLD CTL
Activates the DC Hold or DC braking function.
NOT SEL
2105
DC HOLD SPEED
Defines the DC hold speed.
5
2106
DC CURR REF
Defines the DC hold current.
30
2107
DC BRAKE TIME
Defines the DC brake time.
0
2108
START INHIBIT
Enables the start inhibit function.
OFF
2109
EMER STOP SEL
Selects the source for the external emergency stop command.
NOT SEL
2110
TORQ BOOST CURR
Defines the maximum supplied current during torque boost.
100
2111
STOP SIGNAL DLY
Defines the stop signal delay time when parameter 2102 STOP
FUNCTION is set to SPEED COMP.
0
2112
ZERO SPEED DELAY
Defines the delay for the Zero Speed Delay function.
0
22
ACCEL/DECEL
Acceleration and deceleration times
2201
ACC/DEC 1/2 SEL
Defines the source from which the drive reads the signal that
selects between the two ramp pairs.
DI5
2202
ACCELER TIME 1
Defines the acceleration time 1.
5
2203
DECELER TIME 1
Defines the deceleration time 1.
5
2204
RAMP SHAPE 1
Selects the shape of the acceleration/deceleration ramp 1.
0
2205
ACCELER TIME 2
Defines the acceleration time 2.
60
2206
DECELER TIME 2
Defines the deceleration time 2.
60
2207
RAMP SHAPE 2
Selects the shape of the acceleration/deceleration ramp 2.
0
2208
EMER DEC TIME
Defines the time within the drive is stopped if an emergency stop
is activated.
1
2209
RAMP INPUT 0
Defines the source for forcing the ramp input to zero.
NOT SEL
23
SPEED CONTROL
Speed controller variables.
2301
PROP GAIN
Defines a relative gain for the speed controller.
10
2302
INTEGRATION TIME
Defines an integration time for the speed controller.
39204
2303
DERIVATION TIME
Defines the derivation time for the speed controller.
0
2304
ACC COMPENSATION Defines the derivation time for acceleration/(deceleration)
compensation.
0
2305
AUTOTUNE RUN
Start automatic tuning of the speed controller.
OFF
Parameters – short form list
Index
Name/Selection
Description
Def
Custom
Содержание ACS350 Series
Страница 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Страница 4: ......
Страница 8: ...Safety 8 ...
Страница 18: ...Table of contents 18 ...
Страница 24: ...Hardware description 24 ...
Страница 44: ...Installation checklist 44 ...
Страница 56: ...Start up control with I O and ID Run 56 ...
Страница 140: ...Program features 140 ...
Страница 242: ...Actual signals and parameters 242 ...
Страница 266: ...Fieldbus control with embedded fieldbus 266 ...
Страница 284: ...Fault tracing 284 ...
Страница 288: ...Maintenance and hardware diagnostics 288 ...
Страница 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Страница 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Страница 312: ...Dimensions 312 Frame size R4 IP20 cabinet installation UL open Frame size R4 cabinet installation UL open 3AFE68935644 ...
Страница 313: ......