Fault tracing
277
5029
Memory is not ready.
Retry.
5030
Invalid request
Contact your local ABB representative.
5031
Drive is not ready for operation, e.g due to low DC
voltage.
Check input power supply.
5032
Parameter error
Contact your local ABB representative.
5040
Parameter download error. Selected parameter set
is not in current parameter backup file.
Perform upload function before download.
5041
Parameter backup file does not fit into memory.
Contact your local ABB representative.
5042
Parameter download error. Selected parameter set
is not in current parameter backup file.
Perform upload function before download.
5043
No start inhibit
5044
Parameter backup file restoring error
Check that file is compatible with drive.
5050
Parameter upload aborted
Retry parameter upload.
5051
File error
Contact your local ABB representative.
5052
Parameter upload has failed.
Retry parameter upload.
5060
Parameter download aborted
Retry parameter download.
5062
Parameter download has failed.
Retry parameter download.
5070
Panel backup memory write error
Contact your local ABB representative.
5071
Panel backup memory read error
Contact your local ABB representative.
5080
Operation is not allowed because drive is not in
local control mode.
Switch to local control mode.
5081
Operation is not allowed because of active fault.
Check cause of fault and reset fault.
5082
Operation is not allowed because override mode is
enabled.
5083
Operation is not allowed because parameter lock is
on.
Check parameter
PARAMETER LOCK
setting.
5084
Operation is not allowed because drive is
performing task.
Wait until task is completed and retry.
5085
Parameter download from source to destination
drive has failed.
Check that source and destination drive types
are same, i.e. ACS350. See drive type
designation label.
5086
Parameter download from source to destination
drive has failed.
Check that source and destination drive type
codes are same. See drive type designation
label.
5087
Parameter download from source to destination
drive has failed because parameter sets are
incompatible.
Check that source and destination drive
information are same. See parameters in group
.
5088
Operation has failed because of drive memory
error.
Contact your local ABB representative.
5089
Download has failed because of CRC error.
Contact your local ABB representative.
5090
Download has failed because of data processing
error.
Contact your local ABB representative.
5091
Operation has failed because of parameter error.
Contact your local ABB representative.
5092
Parameter download from source to destination
drive has failed because parameter sets are
incompatible.
Check that source and destination drive
information are same. See parameters in group
.
ALARM CODE
CAUSE
WHAT TO DO
Содержание ACS350 Series
Страница 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Страница 4: ......
Страница 8: ...Safety 8 ...
Страница 18: ...Table of contents 18 ...
Страница 24: ...Hardware description 24 ...
Страница 44: ...Installation checklist 44 ...
Страница 56: ...Start up control with I O and ID Run 56 ...
Страница 140: ...Program features 140 ...
Страница 242: ...Actual signals and parameters 242 ...
Страница 266: ...Fieldbus control with embedded fieldbus 266 ...
Страница 284: ...Fault tracing 284 ...
Страница 288: ...Maintenance and hardware diagnostics 288 ...
Страница 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Страница 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Страница 312: ...Dimensions 312 Frame size R4 IP20 cabinet installation UL open Frame size R4 cabinet installation UL open 3AFE68935644 ...
Страница 313: ......