Actual signals and parameters
218
AI2
Uses analog input 2 for ACT2
2
CURRENT
Uses current for ACT1
3
TORQUE
Uses torque for ACT1
4
POWER
Uses power for ACT1
5
COMM ACT 1
Uses value of signal
PID COMM VALUE 1 for ACT1
6
COMM ACT 2
Uses value of signal
PID COMM VALUE 2 for ACT1
7
FREQ INPUT
Frequency input
8
4017
ACT2 INPUT
Defines the source for actual value ACT2. See also parameter
ACT2
MINIMUM.
AI2
ACT1 INPUT.
4018
ACT1 MINIMUM
Sets the minimum value for ACT1.
Scales the source signal used as the actual value ACT1 (defined by
parameter
ACT1 INPUT). For parameter values 6 (COMM ACT 1) and
7 (COMM ACT 2) scaling is not done.
The ACT minimum and maximum correspond the
MINIMUM AI1 and
MAXIMUM AI1 settings as follows.
A= Normal; B = Inversion (ACT1 minimum > ACT1 maximum)
0
-1000…1000%
Value in percent
1 = 1%
4019
ACT1 MAXIMUM
Defines the maximum value for the variable ACT1 if an analog input is
selected as a source for ACT1. See parameter
ACT1 INPUT. The
minimum (
ACT1 MINIMUM) and maximum settings of ACT1 define how
the voltage/current signal received from the measuring device is converted to
a percentage value used by the process PID controller.
See parameter
ACT1 MINIMUM.
100
-1000…1000%
Value in percent
1 = 1%
4020
ACT2 MINIMUM
ACT1 MINIMUM.
0
-1000…1000%
1 = 1%
4021
ACT2 MAXIMUM
ACT1 MAXIMUM.
100
-1000…1000%
1 = 1%
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
Par 4016
Source
Source min.
Source max.
1
Analog input 1
1301 MINIMUM AI1 1302 MAXIMUM AI1
2
Analog input 2
1301 MINIMUM AI2 1302 MAXIMUM AI2
3
Current
0
2 - nominal current
4
Torque
-2 - nominal torque 2 - nominal torque
5
Power
-2 - nominal power
2 - nominal power
AI
(%)
4019
4018
1301
1302
1301
1302
4018
4019
ACT1
(%)
AI
(%)
ACT1
(%)
A
B
Содержание ACS350 Series
Страница 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Страница 4: ......
Страница 8: ...Safety 8 ...
Страница 18: ...Table of contents 18 ...
Страница 24: ...Hardware description 24 ...
Страница 44: ...Installation checklist 44 ...
Страница 56: ...Start up control with I O and ID Run 56 ...
Страница 140: ...Program features 140 ...
Страница 242: ...Actual signals and parameters 242 ...
Страница 266: ...Fieldbus control with embedded fieldbus 266 ...
Страница 284: ...Fault tracing 284 ...
Страница 288: ...Maintenance and hardware diagnostics 288 ...
Страница 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Страница 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Страница 312: ...Dimensions 312 Frame size R4 IP20 cabinet installation UL open Frame size R4 cabinet installation UL open 3AFE68935644 ...
Страница 313: ......