Actual signals and parameters
230
STATE 8
State is forced to state 8.
8
8406
SEQ LOGIC VAL 1
Defines the source for the logic value 1. Logic value 1 is compared to logic
value 2 as defined by parameter
Logic operation values are used in state transitions. See parameter
ST1 TRIG TO ST N selection LOGIC VAL.
NOT SEL
DI1(INV)
Logic value 1 through inverted digital input DI1(INV)
-1
DI2(INV)
See selection DI1(INV).
-2
DI3(INV)
See selection DI1(INV).
-3
DI4(INV)
See selection DI1(INV).
-4
DI5(INV)
See selection DI1(INV).
-5
NOT SEL
No logic value
0
DI1
Logic value 1 through digital input DI1
1
DI2
See selection DI1.
2
DI3
See selection DI1.
3
DI4
See selection DI1.
4
DI5
See selection DI1.
5
SUPRV1 OVER
Logic value according to supervision parameters
...
. See
parameter group
6
SUPRV2 OVER
Logic value according to supervision parameters
...
. See
parameter group
7
SUPRV3 OVER
Logic value according to supervision parameters
...
. See
parameter group
8
SUPRV1 UNDER
See selection SUPRV 1OVER.
9
SUPRV2 UNDER
See selection SUPRV 2OVER.
10
SUPRV3 UNDER
See selection SUPRV 3OVER.
11
TIMED FUNC 1
Logic value 1 is activated by timed function 1. See parameter group
. 1 = timed function active.
12
TIMED FUNC 2
See selection TIMED FUNC 1.
13
TIMED FUNC 3
See selection TIMED FUNC 1.
14
TIMED FUNC 4
See selection TIMED FUNC 1.
15
8407
SEQ LOGIC OPER 1
Selects the operation between logic value 1 and 2. Logic operation values
are used in state transitions. See parameter
ST1 TRIG TO ST 2 /
ST1 TRIG TO ST N selection LOGIC VAL.
NOT SEL
NOT SEL
Logic value 1 (no logic comparison)
0
AND
Logic function: AND
1
OR
Logic function: OR
2
XOR
Logic function: XOR
3
8408
SEQ LOGIC VAL 2
NOT SEL
8409
SEQ LOGIC OPER 2
Selects the operation between logic value 3 and the result of the first logic
operation defined by parameter
NOT SEL
NOT SEL
Logic value 2 (no logic comparison)
0
AND
Logic function: AND
1
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
Содержание ACS350 Series
Страница 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Страница 4: ......
Страница 8: ...Safety 8 ...
Страница 18: ...Table of contents 18 ...
Страница 24: ...Hardware description 24 ...
Страница 44: ...Installation checklist 44 ...
Страница 56: ...Start up control with I O and ID Run 56 ...
Страница 140: ...Program features 140 ...
Страница 242: ...Actual signals and parameters 242 ...
Страница 266: ...Fieldbus control with embedded fieldbus 266 ...
Страница 284: ...Fault tracing 284 ...
Страница 288: ...Maintenance and hardware diagnostics 288 ...
Страница 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Страница 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Страница 312: ...Dimensions 312 Frame size R4 IP20 cabinet installation UL open Frame size R4 cabinet installation UL open 3AFE68935644 ...
Страница 313: ......