Actual signals and parameters
211
3505
AO EXCITATION
Enables current feed from analog output AO. Parameter setting overrides
parameter group
settings.
With PTC the output current is 1.6 mA.
With Pt 100 the output current is 9.1 mA.
DISABLE
DISABLE
Disabled
0
ENABLE
Enabled
1
36 TIMED FUNCTIONS
Time periods 1 to 4 and booster signal. See section
on
page
3601
TIMERS ENABLE
Selects the source for the timed function enable signal.
NOT SEL
NOT SEL
Timed function is not selected.
0
DI1
Digital input DI. Timed function enable by a rising edge of DI1.
1
DI2
See selection DI1.
2
DI3
See selection DI1.
3
DI4
See selection DI1.
4
DI5
See selection DI1.
5
ACTIVE
Timed function is always enabled.
7
DI1(INV)
Inverted digital input DI1. Timed function enable by a falling edge of DI1.
-1
DI2(INV)
See selection DI1(INV).
-2
DI3(INV)
See selection DI1(INV).
-3
DI4(INV)
See selection DI1(INV).
-4
DI5(INV)
See selection DI1(INV).
-5
3602
START TIME 1
Defines the daily start time 1. The time can be changed in 2 second steps.
00:00:00
00:00:00…23:59:58
hours:minutes:seconds. Example: If parameter value is set to 07:00:00, the
timed function is activated at 7:00 (7 a.m).
3603
STOP TIME 1
Defines the daily stop time 1. The time can be changed in 2 second steps.
00:00:00
00:00:00…23:59:58
hours:minutes:seconds. Example: If parameter value is set to 18:00:00, the
timed function is deactivated at 18:00 (6 p.m).
3604
START DAY 1
Defines the start day 1.
MONDAY
MONDAY
Example: If parameter value is set to MONDAY, timed function 1 is active
from Monday midnight (00:00:00).
1
TUESDAY
2
WEDNESDAY
3
THURSDAY
4
FRIDAY
5
SATURDAY
6
SUNDAY
7
3605
STOP DAY 1
Defines the stop day 1.
MONDAY
See parameter
If parameter is set to FRIDAY, timed function 1 is deactivated on Friday
midnight (23:59:58).
3606
START TIME 2
START TIME 1.
START TIME 1.
3607
STOP TIME 2
STOP TIME 1.
STOP TIME 1.
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
Содержание ACS350 Series
Страница 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Страница 4: ......
Страница 8: ...Safety 8 ...
Страница 18: ...Table of contents 18 ...
Страница 24: ...Hardware description 24 ...
Страница 44: ...Installation checklist 44 ...
Страница 56: ...Start up control with I O and ID Run 56 ...
Страница 140: ...Program features 140 ...
Страница 242: ...Actual signals and parameters 242 ...
Страница 266: ...Fieldbus control with embedded fieldbus 266 ...
Страница 284: ...Fault tracing 284 ...
Страница 288: ...Maintenance and hardware diagnostics 288 ...
Страница 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Страница 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Страница 312: ...Dimensions 312 Frame size R4 IP20 cabinet installation UL open Frame size R4 cabinet installation UL open 3AFE68935644 ...
Страница 313: ......