Start-up, control with I/O and ID Run
53
How to control the drive through the I/O interface
The table below instructs how to operate the drive through the digital and analog
inputs when:
• the motor start-up is performed, and
• the default (standard) parameter settings are valid.
Displays of the Basic Control Panel are shown as an example.
PRELIMINARY SETTINGS
If you need to change the direction of rotation, check that parameter
Ensure that the control connections are wired according to the
connection diagram given for the ABB Standard macro.
See section
on page
Ensure that the drive is in remote control. Press key
to switch
between remote and local control.
In remote control, the panel
display shows text REM.
STARTING AND CONTROLLING THE SPEED OF THE MOTOR
Start by switching digital input DI1 on.
Basic Control Panel: Text FWD starts flashing fast and stops after the
setpoint is reached
Assistant Control Panel: The arrow starts rotating. It is dotted until the
setpoint is reached.
Regulate the drive output frequency (motor speed) by adjusting the
voltage of analog input AI1.
CHANGING THE DIRECTION OF ROTATION OF THE MOTOR
Reverse direction: Switch digital input DI2 on.
Forward direction: Switch digital input DI2 off.
STOPPING THE MOTOR
Switch digital input DI1 off. The motor stops.
Basic Control Panel: Text FWD starts flashing slowly.
Assistant Control Panel: The arrow stops rotating.
LOC
REM
REM Hz
OUTPUT FWD
00
.
REM Hz
OUTPUT FWD
500
.
REM Hz
OUTPUT REV
500
.
REM Hz
OUTPUT FWD
500
.
REM Hz
OUTPUT FWD
00
.
Содержание ACS350 Series
Страница 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Страница 4: ......
Страница 8: ...Safety 8 ...
Страница 18: ...Table of contents 18 ...
Страница 24: ...Hardware description 24 ...
Страница 44: ...Installation checklist 44 ...
Страница 56: ...Start up control with I O and ID Run 56 ...
Страница 140: ...Program features 140 ...
Страница 242: ...Actual signals and parameters 242 ...
Страница 266: ...Fieldbus control with embedded fieldbus 266 ...
Страница 284: ...Fault tracing 284 ...
Страница 288: ...Maintenance and hardware diagnostics 288 ...
Страница 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Страница 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Страница 312: ...Dimensions 312 Frame size R4 IP20 cabinet installation UL open Frame size R4 cabinet installation UL open 3AFE68935644 ...
Страница 313: ......