Actual signals and parameters
171
1506
FILTER AO1
Defines the filter time constant for analog output AO, i.e the time within 63%
of a step change is reached. See figure in parameter
FILTER AI1.
0.1
0.0…10.0 s
Filter time constant
1 = 0.1 s
16 SYSTEM
CONTROLS
Run Enable, parameter lock etc.
1601
RUN ENABLE
Selects a source for the external Run Enable signal.
NOT SEL
NOT SEL
Allows the drive to start without an external Run Enable signal.
0
DI1
External signal required through digital input DI1. 1 = Run Enable. If Run
Enable signal is switched off, the drive will not start or coasts to stop if it is
running.
1
DI2
See selection DI1.
2
DI3
See selection DI1.
3
DI4
See selection DI1.
4
DI5
See selection DI1.
5
COMM
Fieldbus interface as the source for inverted Run Enable signal (Run
Disable), i.e. control word
FB CMD WORD 1 bit 6 (with ABB drives
profile
EFB PAR 19 bit 3). The control word is sent by the fieldbus
controller via the fieldbus adapter or embedded fieldbus (modbus) to the
drive. For the control word bits, see sections
on
and
ABB Drives communication profile
on page
.
7
DI1(INV)
External signal required through inverted digital input DI1. 0 = Run Enable.
If Run Enable signal is switched on, the drive will not start or coasts to stop if
it is running.
-1
DI2(INV)
See selection DI1(INV)
-2
DI3(INV)
See selection DI1(INV)
-3
DI4(INV)
See selection DI1(INV)
-4
DI5(INV)
See selection DI1(INV)
-5
1602
PARAMETER LOCK
Selects the state of the parameter lock. The lock prevents parameter
changing from control panel.
OPEN
LOCKED
Parameter values cannot be changed from the control panel. The lock can be
opened by entering the valid code to parameter
PASS CODE.
The lock does not prevent parameter changes made by macros or fieldbus.
0
OPEN
The lock is open. Parameter values can be changed.
1
NOT SAVED
Parameter changes made by control panel are not stored into the permanent
memory. To store changed parameter values, set parameter
PARAM
SAVE value to SAVE.
2
1603
PASS CODE
Selects the pass code for the parameter lock (see parameter
PARAMETER LOCK).
0
0…65535
Pass code. Setting 358 opens the lock. The value reverts back to 0
automatically.
1 = 1
1604
FAULT RESET SEL
Selects the source for the fault reset signal. The signal resets the drive after a
fault trip if the cause of the fault no longer exists.
KEYPAD
KEYPAD
Fault reset only from the control panel
0
DI1
Reset through digital input DI1 (reset by a rising edge of DI1) or by control
panel
1
DI2
See selection DI1.
2
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
Содержание ACS350 Series
Страница 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Страница 4: ......
Страница 8: ...Safety 8 ...
Страница 18: ...Table of contents 18 ...
Страница 24: ...Hardware description 24 ...
Страница 44: ...Installation checklist 44 ...
Страница 56: ...Start up control with I O and ID Run 56 ...
Страница 140: ...Program features 140 ...
Страница 242: ...Actual signals and parameters 242 ...
Страница 266: ...Fieldbus control with embedded fieldbus 266 ...
Страница 284: ...Fault tracing 284 ...
Страница 288: ...Maintenance and hardware diagnostics 288 ...
Страница 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Страница 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Страница 312: ...Dimensions 312 Frame size R4 IP20 cabinet installation UL open Frame size R4 cabinet installation UL open 3AFE68935644 ...
Страница 313: ......