Actual signals and parameters
166
DI2,3(INV)
See selection DI1,2(INV).
-8
DI3,4(INV)
See selection DI1,2(INV).
-9
DI4,5(INV)
See selection DI1,2(INV).
-10
DI1,2,3(INV)
Constant speed selection through inverted digital inputs DI1, DI2 and DI3. 1 =
DI active, 0 = DI inactive.
-12
DI3,4,5(INV)
See selection DI1,2,3(INV).
-13
1202
CONST SPEED 1
Defines constant speed (or drive output frequency) 1.
Eur: 5 / US: 6
0.0…500.0 Hz /
0…30000 rpm
Speed in rpm. Output frequency in Hz if parameter
MOTOR CTRL
MODE setting is SCALAR:FREQ.
1 = 0.1 Hz /
1 rpm
1203
CONST SPEED 2
Defines constant speed (or drive output frequency) 2.
Eur: 10 / US:
12
0.0…500.0 Hz /
0…30000 rpm
Speed in rpm. Output frequency in Hz if parameter
MOTOR CTRL
MODE setting is SCALAR:FREQ.
1 = 0.1 Hz /
1 rpm
1204
CONST SPEED 3
Defines constant speed (or drive output frequency) 3.
Eur: 15 / US:
18
0.0…500.0 Hz /
0…30000 rpm
Speed in rpm. Output frequency in Hz if parameter
MOTOR CTRL
MODE setting is SCALAR:FREQ.
1 = 0.1 Hz /
1 rpm
1205
CONST SPEED 4
Defines constant speed (or drive output frequency) 4.
Eur: 20 / US:
24
0.0…500.0 Hz /
0…30000 rpm
Speed in rpm. Output frequency in Hz if parameter
MOTOR CTRL
MODE setting is SCALAR:FREQ.
1 = 0.1 Hz /
1 rpm
1206
CONST SPEED 5
Defines constant speed (or drive output frequency) 5.
Eur: 25 / US:
30
0.0…500.0 Hz /
0…30000 rpm
Speed in rpm. Output frequency in Hz if parameter
MOTOR CTRL
MODE setting is SCALAR:FREQ.
1 = 0.1 Hz /
1 rpm
1207
CONST SPEED 6
Defines constant speed (or drive output frequency) 6.
Eur: 40 / US:
48
0.0…500.0 Hz /
0…30000 rpm
Speed in rpm. Output frequency in Hz if parameter
MOTOR CTRL
MODE setting is SCALAR:FREQ. Constant speed 6 is used also as jogging
speed. See section
on page
1 = 0.1 Hz /
1 rpm
1208
CONST SPEED 7
Defines constant speed (or drive output frequency) 7. Constant speed 7 is
used also as jogging speed (see section
on page
) or with fault
functions (
PANEL COMM ERR).
Eur: 50 / US:
60
0…500 Hz /
0…30000 rpm
Speed in rpm. Output frequency in Hz if parameter
MOTOR CTRL
MODE setting is SCALAR:FREQ. Constant speed 7 is used also as jogging
speed. See section
on page
1 = 0.1 Hz /
1 rpm
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
DI1 DI2 DI3 Operation
1
1
1 No constant speed
0
1
1 Speed defined by parameter
CONST SPEED 1
1
0
1 Speed defined by parameter
CONST SPEED 2
0
0
1 Speed defined by parameter
CONST SPEED 3
1
1
0 Speed defined by parameter
CONST SPEED 4
0
1
0 Speed defined by parameter
CONST SPEED 5
1
0
0 Speed defined by parameter
CONST SPEED 6
0
0
0 Speed defined by parameter
CONST SPEED 7
Содержание ACS350 Series
Страница 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Страница 4: ......
Страница 8: ...Safety 8 ...
Страница 18: ...Table of contents 18 ...
Страница 24: ...Hardware description 24 ...
Страница 44: ...Installation checklist 44 ...
Страница 56: ...Start up control with I O and ID Run 56 ...
Страница 140: ...Program features 140 ...
Страница 242: ...Actual signals and parameters 242 ...
Страница 266: ...Fieldbus control with embedded fieldbus 266 ...
Страница 284: ...Fault tracing 284 ...
Страница 288: ...Maintenance and hardware diagnostics 288 ...
Страница 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Страница 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Страница 312: ...Dimensions 312 Frame size R4 IP20 cabinet installation UL open Frame size R4 cabinet installation UL open 3AFE68935644 ...
Страница 313: ......