9.6 Autotuning without Host Reference
9.6.6 Automatically Adjusted Function Settings
9-31
9
T
uning
9.6.6
Automatically Adjusted Function Settings
You can specify whether to automatically adjust the following functions during autotuning.
Automatic Notch Filters
Normally, set Pn460 to n.
1
(Adjust automatically) (default setting).
Vibration will be detected during autotuning without a host reference and a notch filter will be
adjusted.
Set Pn460 to n.
0
(Do not adjust automatically) only if you do not change the setting of
the notch filter before you execute this function.
Anti-Resonance Control Adjustment
This function reduces low vibration frequencies, for which the notch filters cannot be used.
Normally, set Pn160 to n.
1
(Adjust automatically) (default setting).
Vibration will be detected during autotuning without a host reference and anti-resonance con-
trol will be automatically adjusted.
Vibration Suppression
You can use vibration suppression to suppress transitional vibration at a low frequency from 1
Hz to 100 Hz, which is generated mainly when the machine vibrates during positioning.
Normally, set Pn140 to n.
1
(Adjust automatically) (default setting).
Vibration will be detected during autotuning without a host reference and vibration suppression
control will be automatically set.
Set Pn140 = n.
0
(Do not adjust automatically) only if you do not change the settings for
vibration suppression before you execute autotuning without a host reference.
Note: Autotuning without a host reference uses model following control. Therefore, it can be executed only if the
mode is set to 2 or 3.
Parameter
Function
When Enabled
Classification
Pn460
(2460h)
n.
0
Do not adjust the first stage notch filter auto-
matically during execution of autotuning with-
out a host reference, autotuning with a host
reference, and custom tuning.
Immediately
Tuning
n.
1
(default setting)
Adjust the first stage notch filter automatically
during execution of autotuning without a host
reference, autotuning with a host reference,
and custom tuning.
n.
0
Do not adjust the second stage notch filter
automatically when the tuning-less function is
enabled or during execution of autotuning
without a host reference, autotuning with a
host reference, and custom tuning.
n.
1
(default setting)
Adjust the second stage notch filter automati-
cally when the tuning-less function is enabled
or during execution of autotuning without a
host reference, autotuning with a host refer-
ence, and custom tuning.
Parameter
Function
When Enabled
Classification
Pn160
(2160h)
n.
0
Do not adjust anti-resonance control automat-
ically during execution of autotuning without a
host reference, autotuning with a host refer-
ence, and custom tuning.
Immediately
Tuning
n.
1
(default setting)
Adjust anti-resonance control automatically
during execution of autotuning without a host
reference, autotuning with a host reference,
and custom tuning.