7.13 Forcing the Motor to Stop
7.13.3 Resetting Method for Forced Stops
7-57
7
Application Functions
7.13.3
Resetting Method for Forced Stops
This section describes the reset methods that can be used after stopping operation for an
FSTP (Forced Stop Input) signal.
If the FSTP (Forced Stop Input) signal is OFF and the Servo ON command (Enable Operation
command) is input, the forced stop state will be maintained even after the FSTP signal is turned
ON.
Send the Servo OFF command (Disable Operation command) to place the SERVOPACK in the
base block (BB) state and then send the Servo ON command (Enable Operation command).
Enable
Operation
Controlword
(6040h)
Enable
Operation
Disable
Operation
Statusword
(6041h)
Operation
enabled
Switched
on
Operation
enabled
Forced stop state:
FSTP is displayed.
BB state
Operating state
SERVOPACK
state
OFF
(forced stop request)
ON (normal operation)
FSTP signal
ON (normal operation)