7 Wiring
7.2.1 Main Circuit
7-20
(1) Wire Sizes and Tightening Torques
Power Regeneration Converter
Input Voltage
Model:
CACP-JU
Terminal
Symbols
Terminal Screw
Tightening
Torque [N
x
m]
Wire Sizes
Three-phase,
200 VAC
15A3
L1, L2, L3
M6
2.5 to 3.0
AWG6
B1, B2
M5
2.0 to 2.4
AWG14
M5
2.0 to 2.4
AWG6
19A3
L1, L2, L3
M6
2.5 to 3.0
AWG4
B1, B2
M5
2.0 to 2.4
AWG14
M5
2.0 to 2.4
AWG4
22A3
L1, L2, L3
M6
2.5 to 3.0
AWG3
B1, B2
M5
2.0 to 2.4
AWG14
M5
2.0 to 2.4
AWG4
30A3
L1, L2, L3
M6
2.5 to 3.0
AWG2
B1, B2
M5
2.0 to 2.4
AWG14
M6
2.5 to 3.0
AWG4
45A3B
L1, L2, L3
M10
30
AWG3/0
B1, B2
M5
2.0 to 2.4
AWG14
M6
2.5 to 3.0
AWG1/0
Three-phase,
400 VAC
15D3
L1, L2, L3
M6
2.5 to 3.0
AWG8
B1, B2
M5
2.0 to 2.4
AWG14
M5
2.0 to 2.4
AWG7
19D3
L1, L2, L3
M6
2.5 to 3.0
AWG8
B1, B2
M5
2.0 to 2.4
AWG14
M5
2.0 to 2.4
AWG7
22D3
L1, L2, L3
M6
2.5 to 3.0
AWG7
B1, B2
M5
2.0 to 2.4
AWG14
M5
2.0 to 2.4
AWG7