262
Troubleshooting
DME32—Owner’s Manual
A component parameter
is being adjusted
unknowingly.
Is the parameter being adjusted in conjunction with another parameter in a link
group? See “Linking Component Parameters” on page 78.
Is the parameter assigned to a MIDI Control Change and responding to external
MIDI messages? See “Assigning Component Parameters to Control Changes” on
page 246.
Is the parameter responding to Parameter Change messages from an external
MIDI device? See “Component Parameters & Parameter Changes” on page 248.
Is the parameter assigned to a GPI input? See “Assigning GPI Inputs” on
page 214.
Cannot store or recall
scenes or edit component
parameters.
Is Full Protect mode enabled? See “Using Full Protect” on page 205.
Can recall scenes but
cannot store them or edit
component parameters.
Is Scene Recall Only mode enabled? See “Using Scene Recall Only” on page 204.
Forgotten the DME32
password.
See “Initializing the DME32” on page 210.
Cannot transmit or
receive MIDI messages.
Check the MIDI connections.
Make sure the connected MIDI device is turned on and set to transmit and
receive on the selected MIDI Channels.
Check the settings on the MIDI Setup window. See “MIDI Settings” on page 242.
MIDI Program Change
messages do not recall
scenes.
Make sure that the DME32 is set to receive Program Change messages and that
the MIDI Receive Channel setting is correct. See “MIDI Settings” on page 242.
Remember that only scenes that contain data can be recalled.
MIDI Control Change
messages do not control
component parameters.
Make sure that the DME32 is set to receive Control Change messages and that
the MIDI Receive Channel setting is correct. See “MIDI Settings” on page 242.
Check that the Control Change being transmitted is assigned to a component
parameter. See “Assigning Component Parameters to Control Changes” on
page 246.
MIDI Parameter Change
messages do not control
component parameters.
In a multiple-unit system,
the wordclock source can
only be set on DME32 #1.
This is correct. The other DME32s automatically receive their wordclock signals
via the cascade connections.
The EMERGENCY
indicator is lit.
This is because the GPI input assigned to emergency has been triggered. Investi-
gate the cause and remove the emergency condition. See “Emergency Mode”
on page 220.
Multiple-unit operation
does not work.
Check the cascade connections between the DME32s. See “Cascade Connec-
tions” on page 237.
Symptom
Advice