Faults, causes and remedies
en
Installation and operating instructions Wilo DD-I
165
Code
Type
Fault
Cause
Remedy
4025
C
FC Line Warning
Mains connection: excessive phase
asymmetry
Have the electrical connection at the frequency
converter checked by a qualified electrician.
Have the electrical connection at the motor
checked by a qualified electrician.
4025
C
FC Line Warning
Motor connection: one phase is
missing
Have the electrical connection at the frequency
converter checked by a qualified electrician.
Have the electrical connection at the motor
checked by a qualified electrician.
4026
C
FC DC Circuit Warning
Overvoltage
Extend ramp time for brake ramp.
4026
C
FC DC Circuit Warning
Undervoltage
Have the electrical connection at the frequency
converter checked by a qualified electrician.
Check the pre-charge circuit.
4027
C
FC Supply Warning
No supply voltage at frequency
converter
Have the electrical connection at the frequency
converter checked by a qualified electrician.
4027
C
FC Supply Warning
External 24 VDC supply overloaded
Have the electrical connection at the frequency
converter checked by a qualified electrician.
4027
C
FC Supply Warning
1.8 VDC supply of the control card
outside tolerance range.
Have the electrical connection at the frequency
converter checked by a qualified electrician.
4028
C
FC Communication
Warning
Control word timeout
Check Ethernet connection.
Increase parameter 8-03 "Control Timeout Time" in
frequency converter.
Check communication device function.
Check if wiring is EMC-compliant.
4029
C
General FC Warning
"Terminal 50" frequency converter:
Voltage <10 V
Remove cable at "terminal 50":
- If the frequency converter no longer shows the
warning, there is a problem with the customer's
wiring.
- If the frequency converter continues to show the
warning, replace the control card.
4029
C
General FC Warning
No motor connected to the fre-
quency converter output.
Connect motor.
4029
C
General FC Warning
Motor overload
Motor overheated, check cooling and operating
conditions.
Check motor for mechanical overload.
4029
C
General FC Warning
Speed limit reached.
Check operating conditions.
4029
C
General FC Warning
Voltage limit reached.
Check operating conditions.
4029
C
General FC Warning
Temperature of the frequency con-
verter too cold for operation.
Check temperature sensor in frequency converter.
Check sensor cable between IGBT and Gate actu-
ation card.
4030
C
EXIO Communication
Down
Communication with I/O module
failed.
Check the I/O module settings at the Digital Data
Interface.
Check the settings in the I/O module.
Check Ethernet connection.
4031
C
FC Communication
Down
Communication with frequency
converter failed.
Check the frequency converter settings at the Di-
gital Data Interface.
Check settings in the frequency converter.
Check Ethernet connection.
4034
C
Leakage Detected 1
Leakage detected in leakage cham-
ber.
Drain leakage chamber.
4035
C
Leakage Detected 2
Leakage detected in sealing cham-
ber.
Change the oil in the sealing chamber.
Summary of Contents for DD-I
Page 2: ......
Page 3: ...3 Chinese simplified 4 English 96 ...
Page 5: ...zh CHS 安装及操作说明 Wilo DD I 5 9 1 现场总线 参数概览 69 9 2 LSI 系统模式的示例电路图 88 ...
Page 89: ...附录 zh CHS 安装及操作说明 Wilo DD I 89 另请参见 2 LSI系统模式 不带Ex的连接示例 90 2 LSI系统模式 Ex的连接示例 93 ...
Page 90: ...zh CHS 附录 90 WILO SE 2020 12 9 2 1 LSI系统模式 不带Ex的连接示例 ...
Page 91: ...附录 zh CHS 安装及操作说明 Wilo DD I 91 ...
Page 92: ...zh CHS 附录 92 WILO SE 2020 12 ...
Page 93: ...附录 zh CHS 安装及操作说明 Wilo DD I 93 9 2 2 LSI系统模式 Ex的连接示例 ...
Page 94: ...zh CHS 附录 94 WILO SE 2020 12 ...
Page 95: ...附录 zh CHS 安装及操作说明 Wilo DD I 95 ...
Page 188: ...en Appendix 188 WILO SE 2020 12 9 2 1 LSI System mode connection ex ample without Ex ...
Page 189: ...Appendix en Installation and operating instructions Wilo DD I 189 ...
Page 190: ...en Appendix 190 WILO SE 2020 12 ...
Page 192: ...en Appendix 192 WILO SE 2020 12 ...
Page 193: ...Appendix en Installation and operating instructions Wilo DD I 193 ...
Page 194: ......
Page 195: ......