Faults, causes and remedies
en
Installation and operating instructions Wilo DD-I
159
8.1
Error types
The Digital Data Interface distinguishes between five different prioritisations for alarm
and warning messages:
ƒ
Alert Type A
ƒ
Alert Type B
ƒ
Warning Type C
ƒ
Warning Type D
ƒ
Message Type I
NOTICE! The functionality of the alarms and warnings depends on the system mode!
8.1.1
Error types: DDI and LPI system
mode
Functionality of the various alarm and warning messages:
ƒ
Alert Type A: The pump is
switched off
in the event of a fault. Reset the alarm signal
manually
:
–
"Reset Error" on the home page
–
Function "Reset" at a digital input of the frequency converter
or
I/O module
–
Corresponding signal via fieldbus
ƒ
Alert Type B: The pump is
switched off
in the event of a fault. When the fault is cor-
rected, the alarm signal is automatically reset.
ƒ
Warning Type C: These warnings can switch a relay output of the frequency con-
verter
or
the I/O module.
ƒ
Warning Type D: These warnings are only displayed and logged.
ƒ
Message Type I: Information about operating status.
8.1.2
Error types: LSI system mode
Functionality of the various alarm and warning messages:
ƒ
Alert Type A: In the event of a fault, the pump is
not
switched off. Reset the alarm
signal
manually
:
–
"Master Reset" on the Master home page
–
Function "Reset" at a digital input of the
I/O modules
–
Corresponding signal via fieldbus
ƒ
Alert Type B: In the event of a fault, the pump is
not
switched off. When the fault is
corrected, the alarm signal is automatically reset.
NOTICE! The dry-running protection always switches off the pump!
ƒ
Warning Type C: These warnings can switch a relay output of the
I/O module
.
ƒ
Warning Type D: These warnings are only displayed and logged.
ƒ
Message Type I: Information about operating status.
8.2
Error codes
Code
Type
Fault
Cause
Remedy
100.x
A
Pump Unit Offline
(SERIAL NUMBER)
The connection to the specified
pump cannot be established.
Check network connection.
Check network settings.
101
A
Master Changed (SERIAL
NUMBER)
The Master pump was changed due
to the predefined change strategy
or a communication error.
Check change strategy in the Master settings.
Check network connection.
200
B
Alarm in Pump (SERIAL
NUMBER)
Alarm at the specified pump.
Check the error log of the specified pump.
201
B
Dry Run
Dry-running level reached
Check the operating parameters of the system.
Check level settings.
Check the settings of the digital inputs.
202
B
High Water
High water level reached
Check the operating parameters of the system.
Check level settings.
Check the settings of the digital inputs.
203
B
Sensor Error
Measured value is outside the
measurement range, sensor defect-
ive.
Contact customer service.
400
C
Warning in Pump
(SERIAL NUMBER)
Warning for the specified pump.
Check the error log of the specified pump.
Summary of Contents for DD-I
Page 2: ......
Page 3: ...3 Chinese simplified 4 English 96 ...
Page 5: ...zh CHS 安装及操作说明 Wilo DD I 5 9 1 现场总线 参数概览 69 9 2 LSI 系统模式的示例电路图 88 ...
Page 89: ...附录 zh CHS 安装及操作说明 Wilo DD I 89 另请参见 2 LSI系统模式 不带Ex的连接示例 90 2 LSI系统模式 Ex的连接示例 93 ...
Page 90: ...zh CHS 附录 90 WILO SE 2020 12 9 2 1 LSI系统模式 不带Ex的连接示例 ...
Page 91: ...附录 zh CHS 安装及操作说明 Wilo DD I 91 ...
Page 92: ...zh CHS 附录 92 WILO SE 2020 12 ...
Page 93: ...附录 zh CHS 安装及操作说明 Wilo DD I 93 9 2 2 LSI系统模式 Ex的连接示例 ...
Page 94: ...zh CHS 附录 94 WILO SE 2020 12 ...
Page 95: ...附录 zh CHS 安装及操作说明 Wilo DD I 95 ...
Page 188: ...en Appendix 188 WILO SE 2020 12 9 2 1 LSI System mode connection ex ample without Ex ...
Page 189: ...Appendix en Installation and operating instructions Wilo DD I 189 ...
Page 190: ...en Appendix 190 WILO SE 2020 12 ...
Page 192: ...en Appendix 192 WILO SE 2020 12 ...
Page 193: ...Appendix en Installation and operating instructions Wilo DD I 193 ...
Page 194: ......
Page 195: ......