Configuration
132
WILO SE 2020-12
Configure pump
1.
Connect pump to DHCP server.
There
must
be a DHCP server in the network for the initial configuration. Digital
Data Interface has been set to DHCP by default. Consequently, all required network
parameters are accessed using the DHCP server.
2.
Set the IP address and subnet of the pump to the specified network configuration.
Settings ➜ Digital Data Interface ➜ Network Interface Settings Network Interface
Settings [
}
138]
3.
Reconnect to the set IP address.
4.
"Regular user" user account: change the default password.
Open sidebar menu and change user profile. Changing the default password for the
"Regular User" user account [
}
137]
5.
Set the time/date.
Set the correct time and date to correctly log all changes in the Digital Data Inter-
face.
Settings ➜ Clock Clock [
}
137]
6.
Set the language.
Settings ➜ Menu Language Menu Language [
}
137]
6.4.2
Initial configuration: System mode
"LPI"
Define a fixed IP address for the following components before starting the initial com-
missioning:
ƒ
I/O module (if available)
ƒ
Frequency converter
ƒ
Pump
ƒ
Notebook/touch panel (Web HMI)
Configure I/O module (if available)
1.
Set signal type of the analogue inputs at the I/O module (set jumper to current or
voltage input).
2.
Set IP address and subnet of the I/O module to the specified network configura-
tion.
See installation and operating instructions of the I/O module.
3.
Connect the I/O module to the network.
NOTICE! Apart from the IP address, the I/O module requires no further software set-
tings!
Configure frequency converter
1.
Connect the frequency converter to the network.
2.
Set the IP address and subnet of the frequency converter to the specified network
configuration.
See installation and operating instructions of the frequency converter: Parameters
12-0
3.
Set operating mode of the frequency converter to "Off".
See installation and operating instructions of the frequency converter: Press the
Off key on the operating part.
Configure pump
1.
Connect pump to DHCP server.
There
must
be a DHCP server in the network for the initial configuration. Digital
Data Interface has been set to DHCP by default. Consequently, all required network
parameters are accessed using the DHCP server.
2.
Set the IP address and subnet of the pump to the specified network configuration.
Settings ➜ Digital Data Interface ➜ Network Interface Settings [
}
138]
3.
Reconnect to the set IP address.
4.
"Regular user" user account: change the default password.
Summary of Contents for DD-I
Page 2: ......
Page 3: ...3 Chinese simplified 4 English 96 ...
Page 5: ...zh CHS 安装及操作说明 Wilo DD I 5 9 1 现场总线 参数概览 69 9 2 LSI 系统模式的示例电路图 88 ...
Page 89: ...附录 zh CHS 安装及操作说明 Wilo DD I 89 另请参见 2 LSI系统模式 不带Ex的连接示例 90 2 LSI系统模式 Ex的连接示例 93 ...
Page 90: ...zh CHS 附录 90 WILO SE 2020 12 9 2 1 LSI系统模式 不带Ex的连接示例 ...
Page 91: ...附录 zh CHS 安装及操作说明 Wilo DD I 91 ...
Page 92: ...zh CHS 附录 92 WILO SE 2020 12 ...
Page 93: ...附录 zh CHS 安装及操作说明 Wilo DD I 93 9 2 2 LSI系统模式 Ex的连接示例 ...
Page 94: ...zh CHS 附录 94 WILO SE 2020 12 ...
Page 95: ...附录 zh CHS 安装及操作说明 Wilo DD I 95 ...
Page 188: ...en Appendix 188 WILO SE 2020 12 9 2 1 LSI System mode connection ex ample without Ex ...
Page 189: ...Appendix en Installation and operating instructions Wilo DD I 189 ...
Page 190: ...en Appendix 190 WILO SE 2020 12 ...
Page 192: ...en Appendix 192 WILO SE 2020 12 ...
Page 193: ...Appendix en Installation and operating instructions Wilo DD I 193 ...
Page 194: ......
Page 195: ......