en
Configuration
140
WILO SE 2020-12
6.5.5.5
LSI Mode System Settings
Combination of up to four pumps in one system.
ƒ
Enable
Activate pump in the system.
Factory setting: off
ƒ
Master IP
Fixed IP address via which the system incl. the system home page can be reached.
The IP address must be specified by the operator! Associating the pumps with the
system is defined by this static IP address. Enter the Master IP for all pumps of a sys-
tem. The master function is automatically assigned to a pump in the system (re-
dundant master pump).
NOTICE! All IP addresses (slave and master) in the same subnet!
6.5.5.6
Limits Temperature Sensors
Overview of potential temperature sensors and limit value input.
Temperature sensor overview
No.
Description
Display
Temp. input 1
Winding temperature 1
Winding Top/Bot 1
Temp. input 2
Winding temperature 2
Winding 2
Temp. input 3
Winding temperature 3
Winding 3
Temp. input 4
Top motor bearing temper-
ature
Bearing Top 4
Temp. input 5
Bottom motor bearing
temperature
Bearing Bot 5
Limit value input
ƒ
Temp. Input 1 - Warning
Limit value for a warning in °C.
Factory setting: default factory setting
Input: 0 °C to default factory setting
ƒ
Temp. Input 1 - Trip
Limit value for pump shutdown in °C.
Factory setting: default factory setting
Input: 0 °C up to factory specification. The value must be 2 °C higher than the warn-
ing limit value.
Key
"1" is a placeholder for input numbers 1 to 5.
6.5.5.7
Limits Vibration Sensors
Overview of potential vibration sensors and inputting limit values.
Vibration sensor overview
No.
Description
Display
Vibration X, Y, Z
Vibration sensor in DDI
VibX, VibY, VibZ
Vibration input 1/input 2
Input for external vibration
sensor
VibHut, VibTop, VibBot
Limit value input
ƒ
Vibration X - Warning
Limit value for a warning in mm/s.
Factory setting: default factory setting
Input: 0 % to default factory setting
ƒ
Vibration X - Trip
Limit value for pump shutdown in mm/s.
Factory setting: default factory setting
Input: 0 % to default factory setting. The value must be 2 % higher than the limit
value for the warning.
Key
"X" represents a placeholder for the input number X, Y, Z, 1 or 2.
Summary of Contents for DD-I
Page 2: ......
Page 3: ...3 Chinese simplified 4 English 96 ...
Page 5: ...zh CHS 安装及操作说明 Wilo DD I 5 9 1 现场总线 参数概览 69 9 2 LSI 系统模式的示例电路图 88 ...
Page 89: ...附录 zh CHS 安装及操作说明 Wilo DD I 89 另请参见 2 LSI系统模式 不带Ex的连接示例 90 2 LSI系统模式 Ex的连接示例 93 ...
Page 90: ...zh CHS 附录 90 WILO SE 2020 12 9 2 1 LSI系统模式 不带Ex的连接示例 ...
Page 91: ...附录 zh CHS 安装及操作说明 Wilo DD I 91 ...
Page 92: ...zh CHS 附录 92 WILO SE 2020 12 ...
Page 93: ...附录 zh CHS 安装及操作说明 Wilo DD I 93 9 2 2 LSI系统模式 Ex的连接示例 ...
Page 94: ...zh CHS 附录 94 WILO SE 2020 12 ...
Page 95: ...附录 zh CHS 安装及操作说明 Wilo DD I 95 ...
Page 188: ...en Appendix 188 WILO SE 2020 12 9 2 1 LSI System mode connection ex ample without Ex ...
Page 189: ...Appendix en Installation and operating instructions Wilo DD I 189 ...
Page 190: ...en Appendix 190 WILO SE 2020 12 ...
Page 192: ...en Appendix 192 WILO SE 2020 12 ...
Page 193: ...Appendix en Installation and operating instructions Wilo DD I 193 ...
Page 194: ......
Page 195: ......