Faults, causes and remedies
162
WILO SE 2020-12
Code
Type
Fault
Cause
Remedy
3004
A/B
Temp. Sensor 3 Trip
Winding temperature limit reached
Check motor for overload.
Check motor cooling.
Check temperature limit values in Digital Data In-
terface and correct if necessary.
3005
A/B
Temp. Sensor 4 Trip
Bearing temperature limit value
reached
For dry well installation: Check ambient temper-
ature, keep to maximum value.
Check temperature limit values in Digital Data In-
terface and correct if necessary.
3006
A/B
Temp. Sensor 5 Trip
Bearing temperature limit value
reached
For dry well installation: Check ambient temper-
ature, keep to maximum value.
Check temperature limit values in Digital Data In-
terface and correct if necessary.
3007
A/B
Motor Overload
Torque limit reached
If the system exceeds the motor's torque limit dur-
ing the acceleration ramp, extend the time for the
acceleration ramp.
If the system exceeds the generator's torque limit
during the brake ramp, extend the time for the
brake ramp.
If the torque limit is reached during operation, in-
crease the torque limit. Make sure the system can
be operated with a higher torque, if necessary, con-
tact customer service.
Excessive motor current consumption, check oper-
ating conditions.
3007
A/B
Motor Overload
Excess current
Disconnect the motor from the mains connection
and turn the shaft by hand. Contact customer ser-
vice if it is not possible to turn the shaft by hand.
Check the motor power/frequency converter con-
figuration. Contact customer service if the motor
power is too high.
Check parameters 1-20 to 1-25 in the frequency
converter for correct motor data and adapt if ne-
cessary.
3008
A/B
Motor Overtemp.
Thermal motor monitoring has
triggered.
Motor overheated, check cooling and operating
conditions.
Check motor for mechanical overload.
Check thermal motor monitoring connection (fre-
quency converter: terminal 33 and terminal 50
(+10 VDC).
Check parameters 1-93 "Thermistor Source" in the
frequency converter if a thermal switch or thermis-
tor is used: Value must correspond to sensor wiring.
4000
C
High Water Detected
Tank fill level has reached a critical
level.
Check installation (e.g. inlet, outlet, level settings).
Check digital input settings.
4001
C
Leakage Input Warning
Leakage detected
Check the external electrode (optional) function.
Change the oil in the sealing chamber.
Check digital input settings.
4002
C
Temp. Sensor 1 Fault
Sensor faulty, measured value out-
side measurement range.
Contact customer service.
4003
C
Temp. Sensor 2 Fault
Sensor faulty, measured value out-
side measurement range.
Contact customer service.
4004
C
Temp. Sensor 3 Fault
Sensor faulty, measured value out-
side measurement range.
Contact customer service.
4005
C
Temp. Sensor 4 Fault
Sensor faulty, measured value out-
side measurement range.
Contact customer service.
Summary of Contents for DD-I
Page 2: ......
Page 3: ...3 Chinese simplified 4 English 96 ...
Page 5: ...zh CHS 安装及操作说明 Wilo DD I 5 9 1 现场总线 参数概览 69 9 2 LSI 系统模式的示例电路图 88 ...
Page 89: ...附录 zh CHS 安装及操作说明 Wilo DD I 89 另请参见 2 LSI系统模式 不带Ex的连接示例 90 2 LSI系统模式 Ex的连接示例 93 ...
Page 90: ...zh CHS 附录 90 WILO SE 2020 12 9 2 1 LSI系统模式 不带Ex的连接示例 ...
Page 91: ...附录 zh CHS 安装及操作说明 Wilo DD I 91 ...
Page 92: ...zh CHS 附录 92 WILO SE 2020 12 ...
Page 93: ...附录 zh CHS 安装及操作说明 Wilo DD I 93 9 2 2 LSI系统模式 Ex的连接示例 ...
Page 94: ...zh CHS 附录 94 WILO SE 2020 12 ...
Page 95: ...附录 zh CHS 安装及操作说明 Wilo DD I 95 ...
Page 188: ...en Appendix 188 WILO SE 2020 12 9 2 1 LSI System mode connection ex ample without Ex ...
Page 189: ...Appendix en Installation and operating instructions Wilo DD I 189 ...
Page 190: ...en Appendix 190 WILO SE 2020 12 ...
Page 192: ...en Appendix 192 WILO SE 2020 12 ...
Page 193: ...Appendix en Installation and operating instructions Wilo DD I 193 ...
Page 194: ......
Page 195: ......