en
Faults, causes and remedies
160
WILO SE 2020-12
Code
Type
Fault
Cause
Remedy
500
D
Pipe Sedimentation High Blockage in the piping. After detec-
tion, a flushing cycle is started at
maximum frequency for the next
pump cycles.
If the permissible ratio (Admissible
Flow Ratio for Sedimentation) is ex-
ceeded, flushing is terminated.
Check piping, remove blockages.
Check "High Efficiency(HE) Controller" settings.
501
D
Comm. Error I/O Exten-
sion
Communication with I/O module
failed.
Check network connection.
Check I/O module.
Check settings for the I/O module in the Master
settings.
900
I
More than 4 Pumps in
System
Maximum number of pumps in the
system exceeded.
Integrate a maximum of 4 pumps into the system.
901
I
Pump removed from
System (SERIAL NUM-
BER)
Pump has been removed from the
system.
Check network connection.
902
I
Pipe Measurement In-
complete
Calculation of piping parameters
was not successfully executed.
Check settings under High Efficiency(HE) Control-
ler/Pipe Settings and recalculate.
If the message is still displayed, contact customer
service.
903
I
Pipe Calculation Timeout Calculation of piping parameters
was aborted due to a timeout.
Check settings under High Efficiency(HE) Control-
ler/Pipe Settings and recalculate.
If the message is still displayed, contact customer
service.
904
I
Pipe Settings / Calcula-
tion Missing
Calculation of piping parameters has
not yet been carried out. HE con-
troller cannot be activated.
Input settings under High Efficiency(HE) Controller/
Pipe Settings and start calculation.
1000
A
Motor Safe Stop Alarm
"Safe Torque Off" active.
Check connection: 24 VDC must apply at terminal
37 of the frequency converter. A manual reset is re-
quired once the fault has been eliminated!
Installation in potentially explosive atmospheres:
Check switch-off parameters (thermal motor mon-
itoring, dry-running protection).
1001
A
Motor Ground Fault
Alarm
Short circuit to earth between an
output phase and earth (between
frequency converter and motor or
directly in the motor)
Have the electrical connection at the frequency
converter checked by a qualified electrician.
Have the electrical connection at the motor
checked by a qualified electrician.
1002
A
Motor Short Circuit
Alarm
Short circuit in motor or at motor
connection
Have the electrical connection at the motor
checked by a qualified electrician.
2000
B
Motor Vibration X - Trip
Vibration limit value exceeded.
Check pump and installation (e.g. not running
smoothly, poor duty point, distorted installation).
Check vibration limit values in the Digital Data In-
terface and correct if necessary.
2001
B
Motor Vibration Y - Trip
Vibration limit value exceeded.
Check pump and installation (e.g. not running
smoothly, poor duty point, distorted installation).
Check vibration limit values in the Digital Data In-
terface and correct if necessary.
2002
B
Motor Vibration Z - Trip
Vibration limit value exceeded.
Check pump and installation (e.g. not running
smoothly, poor duty point, distorted installation).
Check vibration limit values in the Digital Data In-
terface and correct if necessary.
2003
B
Vibration Input 1 - Trip
Vibration limit value exceeded.
Check pump and installation (e.g. not running
smoothly, poor duty point, distorted installation).
Check vibration limit values in the Digital Data In-
terface and correct if necessary.
Summary of Contents for DD-I
Page 2: ......
Page 3: ...3 Chinese simplified 4 English 96 ...
Page 5: ...zh CHS 安装及操作说明 Wilo DD I 5 9 1 现场总线 参数概览 69 9 2 LSI 系统模式的示例电路图 88 ...
Page 89: ...附录 zh CHS 安装及操作说明 Wilo DD I 89 另请参见 2 LSI系统模式 不带Ex的连接示例 90 2 LSI系统模式 Ex的连接示例 93 ...
Page 90: ...zh CHS 附录 90 WILO SE 2020 12 9 2 1 LSI系统模式 不带Ex的连接示例 ...
Page 91: ...附录 zh CHS 安装及操作说明 Wilo DD I 91 ...
Page 92: ...zh CHS 附录 92 WILO SE 2020 12 ...
Page 93: ...附录 zh CHS 安装及操作说明 Wilo DD I 93 9 2 2 LSI系统模式 Ex的连接示例 ...
Page 94: ...zh CHS 附录 94 WILO SE 2020 12 ...
Page 95: ...附录 zh CHS 安装及操作说明 Wilo DD I 95 ...
Page 188: ...en Appendix 188 WILO SE 2020 12 9 2 1 LSI System mode connection ex ample without Ex ...
Page 189: ...Appendix en Installation and operating instructions Wilo DD I 189 ...
Page 190: ...en Appendix 190 WILO SE 2020 12 ...
Page 192: ...en Appendix 192 WILO SE 2020 12 ...
Page 193: ...Appendix en Installation and operating instructions Wilo DD I 193 ...
Page 194: ......
Page 195: ......