Configuration
en
Installation and operating instructions Wilo DD-I
135
Settings ➜ Frequency Converter ➜ Ramp Settings [
}
141]
12. Assign functions to the inputs/outputs of the frequency converter in the Digital
Data Interface.
Settings ➜ Frequency Converter ➜ Digital Inputs [
}
141]
Settings ➜ Frequency Converter ➜ Relay Outputs [
}
143]
Settings ➜ Frequency Converter ➜ Analog Outputs [
}
143]
13. Start "Automatic motor adjustment" on the frequency converter.
See installation and operating instructions of the frequency converter: Parameters
1-29
CAUTION! Carry out complete "automatic motor adjustment". Reduced "auto-
matic motor adjustment" can lead to wrong results!
NOTICE! After carrying out the "automatic motor adjustment", check the num-
ber of poles of the motor: Parameters 1-39!
Configure system settings
1.
Open the
master home page
of the system.
Enter the Master-IP address or click on the house icon on the Slave home page.
2.
Check settings for time/date.
Settings ➜ Clock [
}
137]
3.
Check language settings.
Settings ➜ Menu Language [
}
137]
4.
Set the type and IP address of the I/O module in the Digital Data Interface.
Settings ➜ I/O Extension ➜ IP / Type Select [
}
144]
5.
Assign functions to I/O module inputs/outputs in the Digital Data Interface.
Settings ➜ I/O Extension ➜ Digital Inputs [
}
144]
Settings ➜ I/O Extension ➜ Analog Inputs [
}
145]
Settings ➜ I/O Extension ➜ Relay Outputs [
}
145]
6.
Select control mode: Auto Mode Selection
Function Modules ➜ Operating Mode ➜ Operating Mode (System) [
}
150]
7.
Set the system limits.
Function Modules ➜ System Limits ➜ Levels [
}
151]
Function Modules ➜ System Limits ➜ Dry Run Sensor Selection [
}
151]
Function Modules ➜ System Limits ➜ Pump Limits and Changer [
}
151]
Function Modules ➜ System Limits ➜ Min/Max Frequency [
}
152]
8.
Configure parameters for control mode:
–
Level Control
Function Modules ➜ Level Controller ➜ Stop Level [
}
153]
Function Modules ➜ Level Controller ➜ Level 1 ... 6 [
}
153]
–
PID
Function Modules ➜ PID Controller ➜ PID Settings [
}
153]
Function Modules ➜ PID Controller ➜ Controller Parameter [
}
154]
–
HE-Controller
Function Modules ➜ High Efficiency(HE) Controller ➜ Control Settings [
}
155]
Function Modules ➜ High Efficiency(HE) Controller ➜ Pipe Settings [
}
155]
NOTICE! If all information about the pipe is stored, carry out "Calculate pip-
ing"!
Function Modules ➜ High Efficiency(HE) Controller ➜ Tank Geometry [
}
156]
Activate pump
NOTICE! Repeat steps 1 – 4 for each pump and frequency converter!
1.
Open the
slave home page
of the pump.
2.
Set frequency converter to "automatic mode".
Summary of Contents for DD-I
Page 2: ......
Page 3: ...3 Chinese simplified 4 English 96 ...
Page 5: ...zh CHS 安装及操作说明 Wilo DD I 5 9 1 现场总线 参数概览 69 9 2 LSI 系统模式的示例电路图 88 ...
Page 89: ...附录 zh CHS 安装及操作说明 Wilo DD I 89 另请参见 2 LSI系统模式 不带Ex的连接示例 90 2 LSI系统模式 Ex的连接示例 93 ...
Page 90: ...zh CHS 附录 90 WILO SE 2020 12 9 2 1 LSI系统模式 不带Ex的连接示例 ...
Page 91: ...附录 zh CHS 安装及操作说明 Wilo DD I 91 ...
Page 92: ...zh CHS 附录 92 WILO SE 2020 12 ...
Page 93: ...附录 zh CHS 安装及操作说明 Wilo DD I 93 9 2 2 LSI系统模式 Ex的连接示例 ...
Page 94: ...zh CHS 附录 94 WILO SE 2020 12 ...
Page 95: ...附录 zh CHS 安装及操作说明 Wilo DD I 95 ...
Page 188: ...en Appendix 188 WILO SE 2020 12 9 2 1 LSI System mode connection ex ample without Ex ...
Page 189: ...Appendix en Installation and operating instructions Wilo DD I 189 ...
Page 190: ...en Appendix 190 WILO SE 2020 12 ...
Page 192: ...en Appendix 192 WILO SE 2020 12 ...
Page 193: ...Appendix en Installation and operating instructions Wilo DD I 193 ...
Page 194: ......
Page 195: ......