Configuration
en
Installation and operating instructions Wilo DD-I
133
Open sidebar menu and change user profile. Changing the default password for the
"Regular User" user account [
}
137]
5.
Set the time/date.
Set the correct time and date to correctly log all changes in the Digital Data Inter-
face.
Settings ➜ Clock [
}
137]
6.
Set the language.
Settings ➜ Menu Language [
}
137]
7.
Set the system mode of the pump to "LPI".
Settings ➜ Digital Data Interface ➜ System Mode Selection [
}
139]
NOTICE! Wait until the page updates!
8.
Set type and IP address of the frequency converter in the Digital Data Interface.
Settings ➜ Frequency Converter ➜ IP / Type Select [
}
141]
9.
Carry out auto-parameterisation.
Settings ➜ Frequency Converter ➜ Auto Setup [
}
141]
10. Set ramp times of the frequency converter in the Digital Data Interface.
Settings ➜ Frequency Converter ➜ Ramp Settings [
}
141]
11. Assign functions to the inputs/outputs of the frequency converter in the Digital
Data Interface.
Settings ➜ Frequency Converter ➜ Digital Inputs [
}
141]
Settings ➜ Frequency Converter ➜ Analog Inputs [
}
142]
Settings ➜ Frequency Converter ➜ Relay Outputs [
}
143]
Settings ➜ Frequency Converter ➜ Analog Outputs [
}
143]
12. Start "Automatic motor adjustment" on the frequency converter.
See installation and operating instructions of the frequency converter: Parameters
1-29
CAUTION! Carry out complete "automatic motor adjustment". Reduced "auto-
matic motor adjustment" can lead to wrong results!
NOTICE! After carrying out the "automatic motor adjustment", check the num-
ber of poles of the motor: Parameters 1-39!
13. Set type and IP address of the I/O module in the Digital Data Interface (if available).
Settings ➜ I/O Extension ➜ IP / Type Select [
}
144]
14. Assign functions to I/O module inputs/outputs in the Digital Data Interface.
Settings ➜ I/O Extension ➜ Digital Inputs [
}
144]
Settings ➜ I/O Extension ➜ Analog Inputs [
}
145] (only Wilo I/O 2)
Settings ➜ I/O Extension ➜ Relay Outputs [
}
145]
Activate pump
1.
Set frequency converter to "automatic mode".
See installation and operating instructions of the frequency converter: Press the
Auto On key on the operating part.
2.
Set pump to "automatic mode".
Function Modules ➜ Operating Mode (Pump) [
}
148]
3.
To be able to use the clogging detection, calibrate the reference curve.
Function Modules ➜ Clog Detection ➜ Clog Detection - Teach Power Curve
[
}
148]
6.4.3
Initial configuration: System mode
"LSI"
Define a fixed IP address for the following components before starting the initial com-
missioning:
ƒ
I/O module
ƒ
For each frequency converter
ƒ
For each pump
ƒ
Master-IP for system access
Summary of Contents for DD-I
Page 2: ......
Page 3: ...3 Chinese simplified 4 English 96 ...
Page 5: ...zh CHS 安装及操作说明 Wilo DD I 5 9 1 现场总线 参数概览 69 9 2 LSI 系统模式的示例电路图 88 ...
Page 89: ...附录 zh CHS 安装及操作说明 Wilo DD I 89 另请参见 2 LSI系统模式 不带Ex的连接示例 90 2 LSI系统模式 Ex的连接示例 93 ...
Page 90: ...zh CHS 附录 90 WILO SE 2020 12 9 2 1 LSI系统模式 不带Ex的连接示例 ...
Page 91: ...附录 zh CHS 安装及操作说明 Wilo DD I 91 ...
Page 92: ...zh CHS 附录 92 WILO SE 2020 12 ...
Page 93: ...附录 zh CHS 安装及操作说明 Wilo DD I 93 9 2 2 LSI系统模式 Ex的连接示例 ...
Page 94: ...zh CHS 附录 94 WILO SE 2020 12 ...
Page 95: ...附录 zh CHS 安装及操作说明 Wilo DD I 95 ...
Page 188: ...en Appendix 188 WILO SE 2020 12 9 2 1 LSI System mode connection ex ample without Ex ...
Page 189: ...Appendix en Installation and operating instructions Wilo DD I 189 ...
Page 190: ...en Appendix 190 WILO SE 2020 12 ...
Page 192: ...en Appendix 192 WILO SE 2020 12 ...
Page 193: ...Appendix en Installation and operating instructions Wilo DD I 193 ...
Page 194: ......
Page 195: ......