Faults, causes and remedies
164
WILO SE 2020-12
Code
Type
Fault
Cause
Remedy
4019
C
Motor Overload
Torque limit reached
If the system exceeds the motor's torque limit dur-
ing the acceleration ramp, extend the time for the
acceleration ramp.
If the system exceeds the generator's torque limit
during the brake ramp, extend the time for the
brake ramp.
If the torque limit is reached during operation, in-
crease the torque limit. Make sure the system can
be operated with a higher torque, if necessary, con-
tact customer service.
Excessive motor current consumption, check oper-
ating conditions.
4019
C
Motor Overload
Excess current
Disconnect the motor from the mains connection
and turn the shaft by hand. Contact customer ser-
vice if it is not possible to turn the shaft by hand.
Check the motor power/frequency converter con-
figuration. Contact customer service if the motor
power is too high.
Check parameters 1-20 to 1-25 in the frequency
converter for correct motor data and adapt if ne-
cessary.
4020
C
Motor Overtemp.
Thermal motor monitoring has
triggered.
Motor overheated, check cooling and operating
conditions.
Check motor for mechanical overload.
Check thermal motor monitoring connection (fre-
quency converter: terminal 33 and terminal 50
(+10 VDC).
Check parameters 1-93 "Thermistor Source" in the
frequency converter if a thermal switch or thermis-
tor is used: Value must correspond to sensor wiring.
4022
C
Motor Safe Stop Warn-
ing
"Safe Torque Off" active.
Check connection: 24 VDC must apply at terminal
37 of the frequency converter. A manual reset is re-
quired once the fault has been eliminated!
Installation in potentially explosive atmospheres:
Check switch-off parameters (thermal motor mon-
itoring, dry-running protection).
4024
C
FC Overload Warning
Temperature sensor of the perform-
ance card records excessive or in-
sufficient temperature.
Check frequency converter ventilation.
4024
C
FC Overload Warning
Switch-off temperature (75 °C) of
the control card reached.
Check frequency converter ventilation.
4024
C
FC Overload Warning
Inverter overload
Compare rated current:
- Compare output current displayed at LCP with
rated current of the frequency converter
- Compare the output current displayed at the LCP
with measured motor current
Display thermal load on LCP and monitor value:
- If the frequency converter is operated
above
the
permanent rated current, the counter increases.
- If the frequency converter is operated
below
the
permanent rated current, the counter decreases.
Check parameters 1-20 to 1-25 in the frequency
converter for correct motor data and adapt if ne-
cessary.
4025
C
FC Line Warning
Mains connection: one phase is
missing
Have the electrical connection at the frequency
converter checked by a qualified electrician.
Have the electrical connection at the motor
checked by a qualified electrician.
Summary of Contents for DD-I
Page 2: ......
Page 3: ...3 Chinese simplified 4 English 96 ...
Page 5: ...zh CHS 安装及操作说明 Wilo DD I 5 9 1 现场总线 参数概览 69 9 2 LSI 系统模式的示例电路图 88 ...
Page 89: ...附录 zh CHS 安装及操作说明 Wilo DD I 89 另请参见 2 LSI系统模式 不带Ex的连接示例 90 2 LSI系统模式 Ex的连接示例 93 ...
Page 90: ...zh CHS 附录 90 WILO SE 2020 12 9 2 1 LSI系统模式 不带Ex的连接示例 ...
Page 91: ...附录 zh CHS 安装及操作说明 Wilo DD I 91 ...
Page 92: ...zh CHS 附录 92 WILO SE 2020 12 ...
Page 93: ...附录 zh CHS 安装及操作说明 Wilo DD I 93 9 2 2 LSI系统模式 Ex的连接示例 ...
Page 94: ...zh CHS 附录 94 WILO SE 2020 12 ...
Page 95: ...附录 zh CHS 安装及操作说明 Wilo DD I 95 ...
Page 188: ...en Appendix 188 WILO SE 2020 12 9 2 1 LSI System mode connection ex ample without Ex ...
Page 189: ...Appendix en Installation and operating instructions Wilo DD I 189 ...
Page 190: ...en Appendix 190 WILO SE 2020 12 ...
Page 192: ...en Appendix 192 WILO SE 2020 12 ...
Page 193: ...Appendix en Installation and operating instructions Wilo DD I 193 ...
Page 194: ......
Page 195: ......