Faults, causes and remedies
en
Installation and operating instructions Wilo DD-I
161
Code
Type
Fault
Cause
Remedy
2004
B
Vibration Input 2 - Trip
Vibration limit value exceeded.
Check pump and installation (e.g. not running
smoothly, poor duty point, distorted installation).
Check vibration limit values in the Digital Data In-
terface and correct if necessary.
2005
B
FC Overload Alarm
Temperature sensor of the perform-
ance card records excessive or in-
sufficient temperature.
Check frequency converter ventilation.
2005
B
FC Overload Alarm
Switch-off temperature (75 °C) of
the control card reached.
Check frequency converter ventilation.
2005
B
FC Overload Alarm
Inverter overload
Compare rated current:
- Compare output current displayed at LCP with
rated current of the frequency converter
- Compare the output current displayed at the LCP
with measured motor current
Display thermal load on LCP and monitor value:
- If the frequency converter is operated
above
the
permanent rated current, the counter increases.
- If the frequency converter is operated
below
the
permanent rated current, the counter decreases.
2006
B
FC Line Alarm
Mains connection: one phase is
missing
Have the electrical connection at the frequency
converter checked by a qualified electrician.
Have the electrical connection at the motor
checked by a qualified electrician.
2006
B
FC Line Alarm
Mains connection: excessive phase
asymmetry
Have the electrical connection at the frequency
converter checked by a qualified electrician.
Have the electrical connection at the motor
checked by a qualified electrician.
2006
B
FC Line Alarm
Motor connection: one phase is
missing
Have the electrical connection at the frequency
converter checked by a qualified electrician.
Have the electrical connection at the motor
checked by a qualified electrician.
2007
B
FC DC Circuit Alarm
Overvoltage
Extend ramp time for brake ramp.
2007
B
FC DC Circuit Alarm
Undervoltage
Have the electrical connection at the frequency
converter checked by a qualified electrician.
Check the pre-charge circuit.
2008
B
FC Supply Alarm
No supply voltage at frequency
converter
Have the electrical connection at the frequency
converter checked by a qualified electrician.
2008
B
FC Supply Alarm
External 24 VDC supply overloaded
Have the electrical connection at the frequency
converter checked by a qualified electrician.
2008
B
FC Supply Alarm
1.8 VDC supply of the control card
outside tolerance range.
Have the electrical connection at the frequency
converter checked by a qualified electrician.
3000
A/B
Dry Run Detected
Tank fill level has reached a critical
level.
Check installation (e.g. inlet, outlet, level settings).
Check digital input settings.
3001
A/B
Leakage Input Alarm
Leakage detected
Check the external electrode (optional) function.
Change the oil in the sealing chamber.
Check digital input settings.
3002
A/B
Temp. Sensor 1 Trip
Winding temperature limit reached
Check motor for overload.
Check motor cooling.
Check temperature limit values in Digital Data In-
terface and correct if necessary.
3003
A/B
Temp. Sensor 2 Trip
Winding temperature limit reached
Check motor for overload.
Check motor cooling.
Check temperature limit values in Digital Data In-
terface and correct if necessary.
Summary of Contents for DD-I
Page 2: ......
Page 3: ...3 Chinese simplified 4 English 96 ...
Page 5: ...zh CHS 安装及操作说明 Wilo DD I 5 9 1 现场总线 参数概览 69 9 2 LSI 系统模式的示例电路图 88 ...
Page 89: ...附录 zh CHS 安装及操作说明 Wilo DD I 89 另请参见 2 LSI系统模式 不带Ex的连接示例 90 2 LSI系统模式 Ex的连接示例 93 ...
Page 90: ...zh CHS 附录 90 WILO SE 2020 12 9 2 1 LSI系统模式 不带Ex的连接示例 ...
Page 91: ...附录 zh CHS 安装及操作说明 Wilo DD I 91 ...
Page 92: ...zh CHS 附录 92 WILO SE 2020 12 ...
Page 93: ...附录 zh CHS 安装及操作说明 Wilo DD I 93 9 2 2 LSI系统模式 Ex的连接示例 ...
Page 94: ...zh CHS 附录 94 WILO SE 2020 12 ...
Page 95: ...附录 zh CHS 安装及操作说明 Wilo DD I 95 ...
Page 188: ...en Appendix 188 WILO SE 2020 12 9 2 1 LSI System mode connection ex ample without Ex ...
Page 189: ...Appendix en Installation and operating instructions Wilo DD I 189 ...
Page 190: ...en Appendix 190 WILO SE 2020 12 ...
Page 192: ...en Appendix 192 WILO SE 2020 12 ...
Page 193: ...Appendix en Installation and operating instructions Wilo DD I 193 ...
Page 194: ......
Page 195: ......