Configuration
en
Installation and operating instructions Wilo DD-I
151
Specify which controller controls the system.
Factory setting: Level Control
Input: Level Control, PID, HE-Controller
ƒ
Trigger emptying sump
Start manual pump process. The max. specified pumps run up to the specified
switch-off/stop level of the set level detection (see System Limits ➜ Pump Limits
and Changer).
6.6.7
System Limits
Specify the permissible application limits of the system:
ƒ
Levels
Specify the levels for high water and dry-running protection.
ƒ
Dry Run Sensor Selection
Determine the signal source for dry running.
ƒ
Pump Limits and Changer
Settings for regular pump cycling.
ƒ
Min/Max Frequency
Specify the minimum and maximum operating frequency.
ƒ
Start Frequency
Specify an increased operating frequency when starting the pump.
ƒ
Alternative Stop Level
Additional shut-down level for completely draining the pump chamber and aeration
of the level probe.
6.6.7.1
Levels
Define different filling levels for switching the pumps on and off.
NOTICE! Connect a
level sensor for detecting the filling levels!
ƒ
High Water Start Level
If the set level is reached, start the max. specified pumps (see System Limits ➜
Pump Limits and Changer). An entry is made in the Data Logger.
Factory setting: 100 m
Input: 0.05 to 100 m
ƒ
High Water Stop Level
If the set level is reached, all additionally started pumps are switched off. Only those
pumps remain in operation that are required according to the control system. An
entry is made in the Data Logger.
Factory setting: 100 m
Input: 0.05 to 100 m
ƒ
Alternative Start Level
Additional switch-on level for draining the pump chamber earlier. This earlier
switch-on level increases the standby chamber volume for special events, e.g. heavy
rain. To activate the additional switch-on level, assign a digital input on the I/O
module with the function "Alternative Start Level". If the set level is reached, start
the max. specified pumps (see System Limits ➜ Pump Limits and Changer).
Factory setting: 100 m
Input: 0.05 to 100 m
ƒ
Dry Run Level
All pumps are switched off when the set level has been reached. An entry is made in
the Data Logger.
Factory setting: 0.05 m
Input: 0.05 to 100 m
6.6.7.2
Dry Run Sensor Selection
Specify the sensor for the dry run.
ƒ
Sensor Type
Factory setting: Sensor
Input: Sensor, Dry Run Input
–
Sensor
The dry run level is determined via the level sensor.
–
Dry Run Input
The signal for the dry run level is transmitted via a digital input.
Summary of Contents for DD-I
Page 2: ......
Page 3: ...3 Chinese simplified 4 English 96 ...
Page 5: ...zh CHS 安装及操作说明 Wilo DD I 5 9 1 现场总线 参数概览 69 9 2 LSI 系统模式的示例电路图 88 ...
Page 89: ...附录 zh CHS 安装及操作说明 Wilo DD I 89 另请参见 2 LSI系统模式 不带Ex的连接示例 90 2 LSI系统模式 Ex的连接示例 93 ...
Page 90: ...zh CHS 附录 90 WILO SE 2020 12 9 2 1 LSI系统模式 不带Ex的连接示例 ...
Page 91: ...附录 zh CHS 安装及操作说明 Wilo DD I 91 ...
Page 92: ...zh CHS 附录 92 WILO SE 2020 12 ...
Page 93: ...附录 zh CHS 安装及操作说明 Wilo DD I 93 9 2 2 LSI系统模式 Ex的连接示例 ...
Page 94: ...zh CHS 附录 94 WILO SE 2020 12 ...
Page 95: ...附录 zh CHS 安装及操作说明 Wilo DD I 95 ...
Page 188: ...en Appendix 188 WILO SE 2020 12 9 2 1 LSI System mode connection ex ample without Ex ...
Page 189: ...Appendix en Installation and operating instructions Wilo DD I 189 ...
Page 190: ...en Appendix 190 WILO SE 2020 12 ...
Page 192: ...en Appendix 192 WILO SE 2020 12 ...
Page 193: ...Appendix en Installation and operating instructions Wilo DD I 193 ...
Page 194: ......
Page 195: ......